Battery backup reserve: what to set day to day and before a storm

Keep a low everyday battery backup reserve sized to your critical loads, then fill the battery before forecast storms. What Berkeley Lab found, step by step.

Reader question
What backup reserve should I keep on my home battery normally, and when and how should I raise it before severe weather?
A small sailboat rides at its mooring in a harbor with its sail furled tight and a second anchor already set off the bow, as a dark band of cloud gathers over the water.

Keep your everyday backup reserve at the energy your critical loads need to ride through an outage nobody saw coming, which for many homes is a modest share of the battery, and fill the battery a day or two before forecast severe weather. Lawrence Berkeley National Laboratory’s 2024 study found that in nearly every location and rate design it modeled, the bill savings lost by holding a higher everyday reserve outweighed the backup value it added. Automatic storm modes can do the raising for you, but they need the battery online, an accurate home address and, to fill from the grid, permission to charge from the grid.

The rest of this article explains what the reserve setting does on different brands, what Berkeley Lab actually modeled, how to size an everyday reserve from your own loads, and a routine for the days before a storm. Worked examples use the site’s fictional example home and are labeled.

Two settings, not one

A home battery needs two reserve decisions: an everyday level that runs all year, and a storm level that applies only when severe weather is forecast. Treating them as one number forces a bad trade, either a high reserve that wastes the battery on ordinary days or a low one that leaves it half empty when a storm arrives.

Everyday reserve Storm reserve
What it protects against Outages that arrive without warning: a car hits a pole, equipment fails, a short local fault Long outages that come with a forecast: ice storms, hurricanes, high winds, severe thunderstorm lines
Typical length of the protection Hours A day or more
How it is set One percentage in the battery app Raised by hand or by an automatic storm mode, then lowered again
What it costs Energy you cannot use for savings every day Savings lost only on the days it applies, plus any grid energy bought to fill the battery

The split matters because most outage hours come from a few large events. The US Energy Information Administration reported that customers averaged 11 hours of interruptions in 2024, “nearly twice as many as the annual average experienced in the decade before”, and that major events such as Hurricanes Beryl, Helene and Milton accounted for 80% of those hours. Interruptions not triggered by major events “routinely average about two hours per year”. Big storms are usually forecast; the everyday reserve covers the rest.

What a backup reserve does, and what brands call it

A backup reserve is the share of the battery’s usable energy that savings modes are not allowed to spend. When the grid fails, that share becomes available to the circuits the battery backs up. Every major battery app has the setting; the names and the edge cases differ.

What happens to the reserve in an outage

Tesla’s Backup Reserve page, read as a Wayback Machine capture because Tesla’s site refuses automated requests, describes the behavior plainly:

  • The reserve is a portion of stored energy; the remainder is allocated to Self-Powered or Time-Based Control mode.
  • During an outage the reserve becomes available, and depending on the outage’s length the battery “may discharge below your set reserve percentage”.
  • When the outage ends, the battery prioritizes charging back above the reserve before resuming normal operation.
  • Below a 20% setting, the app shows a “Low Backup Reserve” indicator.
  • If an outage starts while stored energy is below 5%, the home loses power immediately, and the battery waits to recharge from solar the next morning.

That last point is the hard floor. A reserve of a few percent is not a small backup; it is effectively no backup until the sun comes up.

Why a 100% reserve turns the savings modes off

The same page states that “setting a backup reserve of 100% prevents use of Self-Powered mode or Time-Based Control mode”, and that doing so “will negatively impact the potential economic benefits of those modes”. A full reserve turns the battery into a backup-only device. That is the right setting for a storm day and an expensive one for an ordinary Tuesday on a time-of-use rate.

Usable capacity already holds some energy back

Manufacturers keep a margin below what the app calls zero. Enphase’s IQ Battery 5P data sheet, for example, footnotes that its 5.0 kWh usable capacity “includes a safety critical limit of 2%” for long outages, and that “an additional 3% capacity is maintained for battery electronic sustenance at night.” Your reserve sits on top of whatever the maker holds back, so 0% on the slider does not mean an empty battery, but it does mean nothing set aside for your loads.

Where the setting lives on different batteries

The reserve has the same job on every brand but sits in different places. On Tesla’s app it is a slider under Settings and then Powerwall, set alongside the operating mode. SolarEdge’s Weather Guard page refers to the system owner’s “Backup Reserve setting” and uses 30% as its example. FranklinWH’s Storm Hedge page tells owners who want extra protection to set a higher “Backup Reserve” ahead of a possible outage. Whatever the label, look for three things in your app: the percentage itself, whether it applies in every operating mode, and whether a storm feature can override it temporarily.

Write the everyday number down. After a software update, a battery replacement or a change of operating mode, check that the setting survived. A reserve that has quietly changed is an easy way to end up with less backup than you chose.

What Berkeley Lab found about everyday reserves

Berkeley Lab’s study concluded that bill savings are more sensitive to the reserve setting than backup value is, and “therefore in most circumstances justify maintaining as low a reserve setting as allowed”. The conditions behind that conclusion matter, because they tell you when it applies to your home and when it does not.

How the study was built

The report, Bill Savings vs. Backup Power by Will Gorman, Galen Barbose, Sunhee Baik, Cesca Miller and Juan Pablo Carvallo (October 2024, funded by DOE’s Solar Energy Technologies Office), simulated home solar plus storage in ten counties: Boston, Tampa, Memphis, Dallas and Fort Worth, Washington, D.C., Duluth, Denver, Seattle, Los Angeles and Phoenix.

  • Outages were generated with Berkeley Lab’s PRESTO model from county-level PowerOutage.US data for roughly 2017 to 2021, with 1,500 simulated years per location.
  • The battery was 10 kWh in the base case (30 kWh as a sensitivity), with 85% round-trip efficiency and a two-hour duration.
  • Rates were generic, not each city’s real tariff: net billing with flat prices, and time-of-use variants with and without grid charging and grid discharging, with a 3 to 7 p.m. weekday peak.
  • Backup value was the energy served during outages times a value of lost load of $5 per kWh in the base case, with sensitivities at $10 and $50.
  • The key assumption: the simulated outages “cannot be anticipated by the customer”. Storms you can see coming are outside the model.

The back-of-the-envelope version

Before the simulations, the report sets out a simple comparison for one kWh of battery capacity. The figure redraws it.

Yearly value of one kWh of battery capacity, held in reserve or used for price arbitrageHeld in reserve, one kWh is worth 7.50 dollars a year at a value of lost load of 5 dollars per kWh and 1.5 interruptions a year. Used for arbitrage, it is worth 13 dollars a year at a 5 cent price difference on 260 weekdays.$0$5$10Dollars per year, per kWh of capacityHeld in reserve$5/kWh × 1.5 outages$7.50Used for arbitrage$0.05/kWh × 260 days$13.00
Back-of-the-envelope comparison from the report's opening section; the authors note that a rigorous comparison depends on outage timing, solar, load and grid-charging rules. Source: Gorman et al., Bill Savings vs. Backup Power, Lawrence Berkeley National Laboratory, October 2024, read November 22, 2026.

Even on a deliberately small 5-cent price spread, using the kWh beats holding it. The simulations explain why the gap persists: reliability value was “fairly insensitive to reserve level”. The simulated outages were mostly short and infrequent, the battery was often fairly full when they began, and solar covered much of the load. In the Memphis base case, total load averaged 11 kWh per outage event, and after solar only about 3 kWh, on average, had to come from the battery’s starting charge.

The finding and its exceptions

Across all ten locations, total value (bill savings plus backup value) “declines monotonically with increasing reserves”. On time-of-use rates without grid discharging, it was “fairly flat up to ~40-50% reserves”, because the battery rarely emptied anyway. The pattern held in worse-than-average outage years, with one modest exception for one rate in Seattle.

Raising the reserve increased total value only when several conditions held together:

  1. Exceptionally poor local reliability, about 10 times the county average.
  2. An exceptionally high value on avoided outages, about 10 times the base case.
  3. A net billing rate, or a time-of-use rate that allows grid discharging but not grid charging.
  4. In some locations, a relatively small price spread on that rate.

What the study leaves out

The authors list the limits themselves. The study:

  • Assumes outages are unannounced. “To the extent customers can anticipate interruptions and adjust their reserves dynamically, the value of maintaining higher default reserve levels will further diminish.” That is the case for a storm routine.
  • Excludes utility battery programs, because owners would adjust reserves around event days.
  • Excludes net metering with flat rates, where a battery earns nothing on the bill and its main value is backup.
  • Uses hourly steps and generic rates, so it is not a cost-effectiveness estimate for any one home.

So the finding supports a low everyday reserve for most homes on time-of-use or net billing rates. It does not cover a home with a medical device that cannot lose power, a home on flat-rate net metering, or the hours before a forecast storm. Those are handled below.

How to choose your everyday reserve

Size the everyday reserve from the loads that must keep running and the hours you want covered before you can react, not from a round number. Four steps get you there.

Step 1: list the loads that must run in the first hours

Write down only what must not stop during the first hours of a surprise outage: the refrigerator, the internet router, some lights, phone charging, a sump pump in a wet season, a gas furnace’s blower in winter, and any medical device. Ready.gov’s power outage guidance asks households to “talk to your medical provider about a power outage plan for medical devices powered by electricity” and to have alternate plans for refrigerating medicines. The battery sizing worksheet adds the list up into watts and kWh per day.

Step 2: decide how many hours to bridge

The everyday reserve only has to carry those loads until something changes: the grid returns, the sun comes up and solar starts recharging, or you shed loads. One night is a useful planning gap, because where the system can recharge from solar during an outage, the morning sun starts refilling the battery. Whether yours is set up that way is a question for the installer.

Step 3: convert hours into kWh and a percentage

Reserve in kWh = average load in kW × hours to bridge ÷ inverter efficiency. Reserve in percent = that kWh ÷ usable capacity.

Example (fictional). The example home’s critical loads average 330 W, and it wants to bridge 8 hours with a 95% efficient inverter. The reserve it needs is 0.33 kW × 8 hours ÷ 0.95 = 2.78 kWh, which is 2.78 ÷ 13.5 = 20.6% of its 13.5 kWh usable battery. Its 20% setting (2.7 kWh) gives 2.7 × 0.95 ÷ 0.33 = 7.8 hours, the result the backup runtime calculator shows for the same inputs.

The table runs the formula for three load levels on a 13.5 kWh battery with a 95% inverter. Read your own row, then round up to the nearest setting the app allows.

Average critical load 4 hours 8 hours 12 hours
330 W (fridge, router, lights, chargers) 1.39 kWh, 10% 2.78 kWh, 21% 4.17 kWh, 31%
600 W (adds a furnace blower or sump pump) 2.53 kWh, 19% 5.05 kWh, 37% 7.58 kWh, 56%
1,000 W (adds a well pump or more heating) 4.21 kWh, 31% 8.42 kWh, 62% 12.63 kWh, 94%

The bottom row shows why a home with large critical loads cannot solve backup with the reserve alone: covering a night at 1 kW needs most of the battery. That home needs a load plan, a larger battery, or both, which is the subject of whole-home vs partial backup.

Step 4: adjust for what you cannot see coming

Raise the everyday reserve above the arithmetic when any of these apply:

  • A medical device that cannot stop. Size for the device alone over the longest gap you would need to arrange another power source.
  • No solar recharging in an outage. If the panels cannot refill the battery when the grid is down, the reserve is all you have until the grid returns.
  • A flat rate with kWh-for-kWh net metering. Berkeley Lab notes that a battery earns no bill savings on that rate design, so a high reserve costs little.
  • A history of frequent unannounced outages on your street. Your own experience is better evidence than a county average.

A check against the study’s outage numbers

Berkeley Lab’s Memphis base case gives a rough sense of scale. The simulated outages there averaged about six hours, and after solar the battery’s starting charge had to cover roughly 3 kWh per event on average. On a 13.5 kWh battery, 3 kWh is 22%. That is close to the 21% the example home’s 8-hour, 330 W calculation produced. It is a sanity check, not a target: the study’s homes were modeled for whole-home backup with generic loads, and your own list decides the number.

What the reserve costs on your rate

A reserve costs money only on days when the savings mode would otherwise have spent that energy. On a time-of-use rate, many days end with energy left in the battery, and a reserve up to that level costs nothing on those days. Above it, every kWh held back is a kWh bought at the peak price.

Example (fictional). On the example home’s clear April weekday, the scheduled battery covers the house from 5 to 9 p.m., delivering 7.2 kWh, and ends the peak with 5.7 kWh stored, 42% of 13.5 kWh. A reserve up to about 42% would have cost nothing that day. Higher reserves cut into the peak:

Reserve kWh held Backup at 330 W, from the reserve alone kWh bought at the 31 cent peak that day Cost that day
20% 2.7 About 7.8 hours 0 $0.00
40% 5.4 About 15.5 hours 0 $0.00
60% 8.1 About 23.3 hours 2.2 $0.69
80% 10.8 About 31.1 hours 4.7 $1.46
100% 13.5 About 38.9 hours 7.2 $2.23

Peak kWh bought = (reserve kWh − 5.7) × 0.922, the battery’s one-way efficiency at 85% round trip, capped at 7.2 kWh. Backup hours = reserve kWh × 0.95 ÷ 0.33. Costs are peak purchases only, before the export credit on solar the battery no longer stores.

On a cloudy or winter day the battery empties further, the free margin shrinks, and the same reserve costs more. On a real tariff the cost per kWh is your peak price. On LG&E’s residential time-of-day rate, RTOD-Energy, that is $0.19307 per kWh (tariff Sheet No. 6, effective September 1, 2026, base charge before riders and taxes). The backup reserve page shows the same trade for the fictional battery as hours of backup against the peak.

The net cost of a reserve kWh on Kentucky rates

The table above counts gross peak purchases. The net cost of holding back one kWh that the battery would otherwise have delivered is the price you now pay for that kWh, minus what the stored energy would have cost to put in. For a solar home, that input cost is the export credit given up, marked up for losses.

Rate (solar charging, export credit $0.07089) Price of the kWh now bought Cost of storing it instead Net cost per kWh of reserve used for backup instead of savings
LG&E RTOD-Energy on-peak $0.19307 $0.07089 ÷ 0.85 = $0.0834 11.0 cents
LG&E Rate RS, any hour $0.11499 $0.0834 3.2 cents
Example rate peak, 31 cents (fictional, 7 cent export) $0.31 $0.07 ÷ 0.85 = $0.0824 22.8 cents

LG&E prices are base energy charges from tariff Sheets No. 5 and 6, effective September 1, 2026; the export credit is the NMS-2 dollar-denominated credit on Sheet No. 58, effective February 16, 2026; all before riders and taxes. On a flat rate with a dollar export credit, a higher reserve costs only a few cents per kWh, which is why the rate design changes the answer. On LG&E’s older NMS-1 rider with Rate RS, which credits exports in kWh, storing solar earns little or nothing on the bill, so a high reserve costs close to nothing.

Automatic storm modes: triggers, targets and requirements

Four battery makers publish a feature that raises the reserve when severe weather is forecast for your address: Tesla Storm Watch, Enphase Storm Guard, SolarEdge Weather Guard and FranklinWH Storm Hedge. Each fills the battery and returns to normal afterward. They differ in what triggers them, how much lead time they take, and what has to be in place for them to work.

FeatureWhat triggers itWhat it doesWhat it needsAfterward
Tesla Storm WatchListed severe-weather alerts for your area: hurricane and tropical storm watches or warnings; warnings for thunderstorms, tornadoes, winter storms, blizzards, ice storms, high wind, floods and othersCharges Powerwall to maximum capacity and holds it until the event endsPhone paired with Powerwall; Grid Charging enabled (its availability is set by the installer by default); accurate home addressReturns to normal behavior; you can opt out per storm or schedule an event by hand
Enphase Storm GuardApproaching storms, by monitoring the National Weather ServiceBatteries automatically fully chargeThe feature turned on in the Enphase AppNot detailed on the page read
SolarEdge Weather GuardSevere weather notifications from the National Weather ServiceAttempts to fully charge on solar and/or grid; activation within 48 hours of the notificationToggle on in the app's Storage screen; listed as compatible with SolarEdge Energy Bank and LG Chem batteriesReturns to the previous reserve (the page's example: 30% to 100% and back to 30%)
FranklinWH Storm HedgeNational Weather Service alerts for your area, chosen from a list of alert typesEnters Emergency Backup mode and charges to maximum capacity; a "backup power duration time before storm" settingEnabled in the app; accurate addressReturns to the previously selected mode; opt out per event
Summarized from manufacturer pages read November 22, 2026: Tesla Storm Watch (Wayback capture of June 8, 2026), Enphase IQ Batteries page, SolarEdge Weather Guard (Wayback capture of March 11, 2023, the latest available), FranklinWH Storm Hedge support page. Features and compatibility change with software updates; check your own app.

Sources: Tesla’s Storm Watch page, Enphase’s IQ Batteries page, SolarEdge’s Weather Guard page and FranklinWH’s Storm Hedge page.

What the trigger means for lead time

The National Weather Service’s definitions of watches and warnings explain why the trigger matters. A Hazardous Weather Outlook describes potential hazards over days 1 through 7. A winter storm watch flags potential hazardous winter weather “within 48 hours”, and a hurricane watch a possible threat “generally within 48 hours”. Hurricane and tropical storm warnings cover winds expected “in 36 hours or less”, and a blizzard warning conditions occurring or expected within the next 12 to 18 hours. A tornado warning is issued when a tornado is imminent, and a severe thunderstorm warning when severe storms are “occurring or imminent”.

A storm mode that reacts to a watch gets a day or more. One that reacts to a thunderstorm warning may get minutes. Tesla’s list, for example, includes watches only for hurricanes and tropical storms; for the other hazards it names warnings. For fast-moving storms, the manual step in the routine below is what fills the battery in time.

How long a fill takes

Example (fictional). The example battery sits at its 2.7 kWh reserve after the evening peak. Filling it to 13.5 kWh adds 10.8 kWh of stored energy. At 85% round trip, one-way charging efficiency is about 92.2%, so it needs 10.8 ÷ 0.922 = 11.7 kWh from the grid. At its 5 kW rating, that takes 11.7 ÷ 5 = 2.3 hours, if the battery charges at its full rating. From solar under storm clouds, it may not fill at all.

Why storm modes need the grid and a connection

Tesla’s page says that before enabling Storm Watch, “your phone must be paired with your Powerwall and Grid Charging must be enabled”. SolarEdge’s page says Weather Guard charges “on solar and/or grid power”. A battery whose interconnection terms do not allow grid charging can fill only from solar, which is the weakest source on the day a storm is coming. If that is your case, start the routine earlier and raise the reserve before the battery spends its solar charge the evening before. The alerts in all four features reach the battery through the maker’s app or online service, so keep the battery’s internet connection working and check that the app has your current address.

Test the storm mode before the season

A storm mode you have never seen trigger is an assumption. Tesla’s page describes a manual option: with Storm Watch enabled, “Schedule Event” lets you choose how long it stays active, which also shows whether the battery actually charges from the grid when asked. Other apps may not offer a manual trigger; in that case, raise the reserve to 100% on a mild off-peak evening and watch the battery’s charging power in the app. If it does not charge from the grid, either the setting is disabled or the interconnection terms do not allow it, and you now know to rely on solar and an earlier start.

A pre-storm routine, from the first forecast to the first outage hour

The routine below assumes you raise the reserve yourself and use any storm mode as a backstop. Each step is tied to a forecast stage the National Weather Service publishes, so the timing adapts to the kind of storm.

Pre-storm battery routine tied to forecast stagesDays 3 to 7 before: an outlook mentions the hazard, so check settings and the critical loads list. About 48 hours before: a watch is issued, so raise the reserve and plan the grid top-up. The night before: fill the battery off-peak, charge the car and phones, chill the freezer. When a warning is issued: shed nonessential loads and confirm backed-up circuits. During the outage: check charge every few hours.Days 3 to 7About 48 hoursNight beforeWarningOutageOutlook:check stormmode, address,load listWatch:raise reserve,plan the gridtop-upFill batteryoff-peak; car,phones, freezerreadyShed largeloads; know thebacked-upcircuitsCheck chargeevery fewhours; shedearlyFast storms skip stages: a thunderstorm warning can arrivewith no watch, so the manual reserve raise is the safety net.
Forecast stages and lead times from the National Weather Service's Warnings defined page; household steps from Ready.gov's Power Outages guidance and manufacturer storm-mode pages, all read November 22, 2026.

Days 3 to 7 out: the outlook

When the local Hazardous Weather Outlook mentions a damaging-wind, ice, flood or tropical threat, check the settings while there is no hurry:

  1. The storm mode is on, the app shows your current address, and the battery reports as online.
  2. Grid charging is enabled, if your interconnection terms allow it. If the setting is missing, ask the installer, because some makers let the installer decide whether it appears.
  3. Your critical loads list and which circuits are on the backup panel are written down where you can find them in the dark.
  4. Any medical device has a plan for an outage longer than the battery can cover.

About 48 hours out: the watch

When a watch covers your area, raise the reserve by hand to the storm level, usually 100%, rather than waiting for the storm mode to trigger. Raising it early stops the savings mode from spending the battery in the next peak. If grid charging is allowed, plan the fill for the next off-peak window so you do not buy at the peak price. The cost of that early raise is one or two days of lost peak savings, at most $2.23 a day for the fictional battery in the table above.

The night before

Let the battery fill off-peak. Then do the household steps that make the stored energy last:

  • Charge the car to your usual daily need plus a margin, and phones, laptops and power banks.
  • Heat the water tank ahead of time if it is electric.
  • Chill the refrigerator and freezer and plan to keep them closed. Ready.gov notes that a refrigerator “will keep food cold for about four hours” and “a full freezer will keep the temperature for about 48 hours” with the doors shut.

When a warning is issued

Turn off large loads that are not on your critical list: the dryer, the oven, EV charging and spare freezers. Know which circuits the battery backs up and confirm what the battery does at the moment the grid drops, so a dark room on an unbacked circuit is not a surprise. On some systems, the backup covers the whole house; on others, a separate panel of selected circuits. The difference is explained in whole-home vs partial backup.

During the outage

Check the battery’s state of charge every few hours and shed loads before it runs low, not after. Ready.gov advises disconnecting appliances and electronics to avoid damage from surges when power returns, and keeping any generator outdoors “at least 20 feet away from windows, doors and attached garages”. The outage readiness checklist collects these steps in one printable list.

Filling the battery before a storm: when to buy and what it costs

Filling the battery from the grid before a storm costs about a dollar or two on most rates if you do it off-peak, and up to three or four times as much at the peak. It is usually the cheapest backup there is.

Example (fictional). Filling the example battery from its 2.7 kWh reserve to full takes 11.7 kWh from the grid, as worked out above. At different prices:

Price paid for the fill Cost of 11.7 kWh
Example rate off-peak, 8 cents (fictional) $0.94
LG&E RTOD-Energy off-peak, $0.09312 $1.09
LG&E Rate RS, $0.11499 at all hours $1.35
LG&E RTOD-Energy on-peak, $0.19307 $2.26
Example rate peak, 31 cents (fictional) $3.63

LG&E prices are base energy charges from tariff Sheets No. 5 and 6, effective September 1, 2026, before riders and taxes. The battery and the example rate are fictional.

Three timing rules follow:

  1. Fill in the off-peak window before the storm, not during the peak the storm happens to arrive in.
  2. Do not discharge the battery in the peak before a storm. On a fast-moving forecast, raise the reserve before the evening peak so the battery keeps what it has.
  3. If you cannot charge from the grid, raise the reserve earlier and let solar fill it on the last clear day.

Grid charging for backup is the same decision as grid charging for savings, made for a different reason. The arithmetic of when it pays on an ordinary day is in should you charge your home battery from the grid?

After the storm: lowering the reserve, seasons and program events

When the storm passes, return to the everyday reserve, or the battery stays a backup-only device and the savings stop. Automatic storm modes do this on their own; a reserve you raised by hand stays raised until you lower it.

Lowering the reserve

Tesla’s Backup Reserve page notes that after an outage the battery “will prioritize charging above your reserve percentage before resuming normal operation”. SolarEdge and FranklinWH describe their storm features returning to the previous reserve or mode when the event ends. If you raised the reserve by hand, put a reminder on your phone for the morning after the watch or warning expires.

If the outage drained the battery

A long outage can leave the battery below its reserve or nearly empty. Tesla’s page describes what happens if an outage begins with stored energy below 5%: the home loses power, and the battery saves that energy and waits to recharge from solar the next morning, then periodically supplies the home until solar can both power the home and recharge it. Once the grid returns, let the battery refill above its reserve before turning large loads back on, and check that the operating mode and reserve are what they were before the storm.

A seasonal everyday reserve

Some homes have an outage season: ice in late winter, thunderstorms in summer, hurricanes in early fall. A slightly higher everyday reserve for those months covers storms that develop faster than a watch can be issued. Base the months on your own outage history and your utility’s outage map, not on a national calendar, and drop back to the lower reserve when the season ends.

Utility program events

If your battery is enrolled in a utility program, the utility may discharge it on event days, and its instructions take priority over your reserve on those days. Berkeley Lab left these programs out of its study for exactly that reason. Before enrolling, read how the program treats your reserve and whether events are suspended when severe weather is forecast. Virtual power plants explains what such programs ask of a battery and what they pay.

How a schedule handles the reserve

A schedule that knows your rate and the forecast can keep the everyday reserve low, raise it ahead of a watch, fill the battery in the cheapest window before the storm, and bring it back down afterward, all without anyone opening an app. It still depends on the battery accepting those instructions and on the interconnection terms allowing grid charging.

Culni is home energy software that reads a home’s electricity rate and runs one daily schedule across rooftop solar, a home battery, EV charging and flexible loads, then checks the result against the bill each month. Its backup reserve feature sets the everyday reserve with you, never schedules the battery below it, and states the hours of backup it gives for the loads you list, at the reserve you choose, along with the daily cost of each storm and seasonal rule. Backup itself depends on the battery, the installation and the state of charge when the outage begins, and device connection is confirmed home by home. The battery homes page explains how backup and savings share one battery.

What to do next

  1. Write down your critical loads and their watts with the battery sizing worksheet.
  2. Pick the hours to bridge for a surprise outage, usually overnight, and compute the everyday reserve: load in kW × hours ÷ 0.95 ÷ usable kWh.
  3. Check what that reserve costs on your rate by looking at how much charge your battery usually has left after the peak. Reserve up to that level is close to free on those days.
  4. Turn on your battery’s storm mode, confirm the address, and confirm grid charging is enabled if your interconnection terms allow it.
  5. Plan the manual step: raise the reserve when a watch is issued, fill the battery off-peak, and lower it when the event ends.
  6. Print the outage readiness checklist and keep it with a flashlight.

The backup runtime calculator converts any reserve into hours for your loads. To have your reserve, storm rules and their daily cost worked out for your own battery and rate, with every assumption written down, you can send your rate and device list.