Whole-home vs partial backup: what a home battery can actually run

Whole home battery backup depends on three limits: continuous and surge power, usable kWh after the reserve, and wiring. What runs, what to shed, what to ask.

Reader question
Will a home battery run my whole house in an outage, or only selected circuits, and what limits that?
A single large garden umbrella shelters a small round table and two chairs in light rain, while the other chairs on the terrace stand wet beyond its edge.

A home battery runs your whole house in an outage only if three limits all allow it: power, energy and wiring. Power is the continuous kW and the few seconds of surge the battery can deliver, which decide whether a central air conditioner or a well pump can start at all. Energy is the usable kWh above your reserve, which decides how long anything runs. Wiring decides which circuits are connected to the battery in the first place. A single battery rated around 4 to 5 kW continuous can carry refrigeration, lights, the network and a gas furnace blower, but large 240-volt loads such as central air, an electric range, a dryer, an electric water heater, heat strips or an EV charger usually need more battery power, load management, or to be left off the backup.

This article takes the three limits one at a time, using two published specification sheets as the reference, then goes through the large loads one by one and works a fictional example both ways. The arithmetic for your own hours of backup belongs to the backup runtime calculator, and the arithmetic for your own load list to the battery sizing worksheet.

Three limits decide what a battery can run

Whole-home and partial backup are not product categories so much as outcomes of three separate limits. A system can pass two and fail the third.

Limit Unit What it decides Where to find it
Continuous power kW or kVA, and amps at 240 V How many loads can run at the same moment The battery’s specification sheet, “rated (continuous) output power”
Surge power Amps or kW for a few seconds, sometimes an LRA figure Whether a motor (air conditioner compressor, well pump, sump pump) can start The same sheet, “peak output”, “surge” or “motor starting” lines
Usable energy kWh, minus your reserve and conversion losses How many hours the running loads last The sheet’s “usable capacity”, your app’s reserve setting
Wiring Which circuits are connected Which loads get power at all The installation drawings, the backup panel’s labels, the installer

Each limit has its own fix. Too little continuous power calls for more battery units or load management. Too little surge calls for a soft starter, a different battery, or excluding the motor. Too little energy calls for more kWh, a higher reserve before storms, or a shorter list. The wrong wiring is a job for a licensed electrician, not a setting.

Power: the continuous rating and what it means in amps

The continuous rating is the most a battery can deliver for as long as it has charge. Add up everything you expect to run at the same moment, convert it to the same units, and compare.

Read the continuous rating on the specification sheet

Two published examples show how ratings are stated:

  • Enphase’s IQ Battery 5P data sheet lists a rated continuous output of 3.84 kVA at 240 V, a rated output current of 16 A, and 5.0 kWh of usable capacity. The same sheet notes that backup and off-grid operation are not supported at 208 V.
  • FranklinWH’s aPower product page lists 13.6 kWh, 5 kW continuous power and 10 kW surge power.

For scale, NREL’s Annual Technology Baseline uses a 5 kW, 12.5 kWh system as its representative residential battery. That makes 5 kW continuous a reasonable starting assumption until you read your own sheet.

A rating in kVA (kilovolt-amperes) is apparent power. For the resistive and mixed household loads that matter here, treating kVA as roughly equal to kW is close enough to sort loads into “fits” and “does not fit”. Your installer works with the exact figures.

Put circuits and batteries in the same units

Household circuits are labeled in amps and volts, batteries in kW. Watts equal volts times amps, so a battery’s continuous rating converts to amps at 240 V: 3.84 kVA ÷ 240 V = 16 A, and 5 kW ÷ 240 V = 20.8 A.

A breaker tells you the most a circuit can ever carry, not what its appliance actually draws. That ceiling is still a fast first screen:

Breaker and voltage Ceiling on the circuit Compared with a 5 kW battery
15 A at 120 V 1.8 kW Fits, with room for other loads
20 A at 120 V 2.4 kW Fits, with room for other loads
20 A at 240 V 4.8 kW Could take nearly all of it at full load
30 A at 240 V 7.2 kW Can exceed it on its own
40 A at 240 V 9.6 kW Can exceed it on its own
50 A at 240 V 12.0 kW Can exceed it on its own

The appliance’s nameplate gives the real draw, and it is usually below the breaker’s ceiling. But the table explains the core problem with whole-home backup on one battery: any single large 240-volt circuit can ask for more than a 5 kW battery can supply, before the refrigerator and the lights are counted.

Add up the loads that can run together

The number to compare with the continuous rating is not the sum of every circuit, but the largest set of loads likely to run at the same moment during an outage. Build it from real scenes:

  1. A winter evening: furnace blower, refrigerator compressor, lights, the microwave or a cooking appliance, and the sump pump if it is raining.
  2. A summer afternoon: the air conditioner, the refrigerator, lights, the network, and whatever someone switches on without thinking, often the dryer or the oven.
  3. A morning: the well pump during showers, the coffee maker, the toaster, the furnace or the air conditioner.

Use each appliance’s running watts from the nameplate or the manual, and for plug-in loads a plug-in energy meter gives better numbers than the label. If the largest scene stays below the continuous rating with some margin, the battery can carry it. If it does not, either the scene must change (a rule such as “no oven while the air conditioner runs”) or the system must.

What happens when the load is too large

A battery will not supply more than its rating for long. What the system does when the house asks for more, whether it limits output, drops the backup circuits or shuts down until reset, depends on the equipment and how it was installed, and is described in the installation manual. Ask the installer what you will see if it happens and how to recover. The practical answer is to make sure it does not: keep the sum of loads that can run together below the continuous rating, by wiring, by load management, or by habit.

Surge: why motor starts decide whole-home backup

Motors draw several times their running current for a moment when they start. A battery that can run an air conditioner may still fail to start it, so the surge rating, not the continuous rating, is often what decides whether central air or a well pump can be on the backup.

Locked rotor amps, in plain terms

Locked rotor amps (LRA) is the current a motor draws at the instant it starts, before the rotor turns. Air conditioner condensers, heat pump outdoor units and many well pumps print it on the nameplate next to the running current. The comparison that matters is the motor’s LRA against the battery’s surge capability, at the same voltage.

Read the surge lines on the sheet

The Enphase IQ Battery 5P data sheet gives three surge figures at 240 V: a peak output current of 32 A for three seconds, 25.6 A for 10 seconds, and a “Power Start capability” of up to 48 A LRA, with a footnote that “Power Start capability may vary.” Its front page summarizes the peak as up to 7.68 kVA, which is 32 A × 240 V. FranklinWH’s aPower page gives 10 kW of surge power and states that a single unit can support home loads while starting a 4-ton air conditioner; it does not give a duration or an LRA figure.

The two sheets describe surge differently, which is why you cannot compare them line by line. Bring the motor’s nameplate LRA to the installer and ask a direct question: can this battery, as installed, start this motor while the other backed-up loads are running?

Specification lineEnphase IQ Battery 5P (per unit)FranklinWH aPower (per unit)What it decides
Usable or rated capacity5.0 kWh usable13.6 kWhHours of backup
Continuous output3.84 kVA at 240 V (16 A)5 kWLoads running at once
Surge or peak32 A for 3 seconds; 25.6 A for 10 seconds (7.68 kVA)10 kW (duration not stated)Motor starts
Motor startingPower Start up to 48 A LRA ("may vary")Starts a 4-ton air conditioner while supporting home loads (maker's statement)Central air, well pumps
Round-trip efficiency90% AC; 96% DCNot stated on the page readEnergy lost on the way in and out
Backup at 208 VNot supportedNot stated on the page readApartment-style 208 V services
Values as published on the Enphase IQ Battery 5P data sheet (DSH-00010-11.0, May 2025) and the FranklinWH aPower product page, both read November 22, 2026. Listed to show how spec sheets state limits, not to compare or recommend products.

Soft starters and other ways to tame a start

A soft starter is a device added to a motor’s starting circuit that ramps the current up instead of letting it jump. On an air conditioner condenser it can bring the start within a battery’s surge capability. Whether one suits your equipment, and whether it affects the equipment’s warranty, is for the HVAC contractor and the equipment maker to answer. The alternatives are a battery system with more surge capability (often by adding units), keeping the motor off the backup, or a load controller that prevents the motor from starting while other large loads run.

Simulation studies tend to hide this limit. Berkeley Lab’s 2024 study of backup reserves, Bill Savings vs. Backup Power, modeled whole-home backup in hourly steps and notes that its analysis “does not consider sub-hourly load spikes”. Hourly arithmetic, including most runtime calculators, cannot tell you whether a compressor will start. Only the surge comparison can.

Energy: usable kWh after the reserve

Power decides what can run together; energy decides for how long. The energy available in an outage is the battery’s usable capacity, at whatever charge it holds when the grid fails, minus conversion losses.

Usable, total and what the maker holds back

Spec sheets list total and usable capacity separately. Usable is the number that matters, and it may already include a margin. The Enphase data sheet footnotes that the IQ Battery 5P’s 5.0 kWh usable capacity “includes a safety critical limit of 2%” for long outages, and that “an additional 3% capacity is maintained for battery electronic sustenance at night.” Read the footnotes on your own sheet before you count kWh.

The reserve is the worst-case starting point

An outage can start right after the evening peak, when the battery has done its daily work and holds only its backup reserve. That is why the reserve, not the full capacity, is the honest starting point for backup arithmetic on ordinary days. Raising the battery to full before a forecast storm changes the starting point; how and when to do that is covered in battery reserve before storms.

The formula

Hours of backup = usable kWh × starting charge × inverter efficiency ÷ average load in kW. The backup runtime calculator runs it with a default 95% inverter efficiency.

The average load is the hard part, because a whole house and a list of critical circuits differ by several times. That is the real difference between whole-home and partial backup: not whether a battery can be wired to everything, but how fast everything empties it.

What a whole house uses in a day

EIA reports that the average US residential customer bought 10,791 kWh of electricity in 2022, about 899 kWh a month. Spread evenly, that is 10,791 ÷ 365 = 29.6 kWh a day, an average load of about 1.23 kW around the clock. EIA adds that for homes with net-metered solar, consumption “may be a lot higher than household electricity purchases”, so a solar home should read its consumption from the inverter or battery app, not from the bill.

Compare that with a battery like the fictional example one, which holds 13.5 kWh usable. A house that uses the national average would empty it, from full, in under half a day with no solar, and a hot or cold day uses more than the average. A short critical list averaging a few hundred watts lasts days on the same battery. Your own number comes from your interval data or your battery app’s home consumption on a day like the one you are planning for.

How much capacity backup buyers choose

Berkeley Lab’s study used a 10 kWh battery in its base case, describing it as roughly “the most-typical battery size observed within the market today”, and ran 30 kWh as a sensitivity that “may be more reflective of how a customer would size its battery for whole-home backup.” The factor of three between those two numbers is a fair picture of what whole-home backup asks of a system that has to cover heating or cooling as well as the basics.

Wiring: the ways backup is connected

How the battery is wired decides which circuits get power when the grid fails, and no app setting changes that. There are four common arrangements, and your installation drawings say which one you have.

Three ways a battery is wired for backupLeft: whole-home backup, where an automatic disconnect between the utility meter and the main panel lets the battery feed every circuit in the main panel. Middle: partial backup, where the battery feeds a separate critical-loads subpanel and the main panel's other circuits go dark. Right: whole-home connection with load management, where the battery feeds the main panel and a controller switches off selected large circuits when needed.Whole-homeCritical-loads subpanelWhole-home, managedMeterDisconnectBatteryMain panel:every circuitbacked upMeterMain panel: darkBatterySubpanel:selectedcircuitsMeterDisconnectBatteryMain panelShed firstby controllerMint: powered by the battery in an outage. Gray: dark in an outage.
Simplified one-line sketches for orientation, not wiring diagrams. Real installations add breakers, gateways and controls, and must follow the electrical code edition adopted where you live. Configuration names follow manufacturer documentation, including the "whole home backup" configuration pictured on the Enphase IQ Battery 5P data sheet; read November 22, 2026.

Whole-home backup at the main panel

In a whole-home arrangement, a device between the utility meter and the main panel opens the connection to the grid when it fails, and the battery then feeds the whole panel. The Enphase data sheet pictures a “whole home backup” configuration that adds an IQ System Controller alongside the batteries and combiner. Every circuit has power, which is the appeal, and every circuit can draw on the battery at once, which is the risk. Without load management, the continuous and surge limits above are enforced only by the household’s habits.

A critical-loads subpanel

In a partial arrangement, the installer moves selected circuits from the main panel into a separate subpanel that the battery feeds. When the grid fails, those circuits stay on and the rest of the house goes dark. The list is fixed at installation, so choose it with the outage in mind, not the sales conversation: the refrigerator, the furnace blower, the sump pump, the network, a few lighting circuits, a bedroom outlet for medical equipment. Changing the list later means an electrician moving breakers.

Whole-home with load management

The middle path wires the battery to the main panel and adds a controller that can switch off selected large circuits automatically. It keeps the convenience of whole-home backup while protecting the battery’s limits. How that shedding decides what to drop is the subject of the next section.

Batteries installed with no backup at all

Some batteries are installed only to shift energy for the bill, with no backup connection. The Enphase data sheet, for example, also pictures a “grid-tied system” made of a combiner and batteries without the system controller used in its whole-home configuration. If your installation documents do not show a backup path, assume there is none and ask the installer before storm season.

How load management decides what to drop

Load management keeps a whole-home system inside its limits by turning off lower-priority circuits when the total gets too high or the battery gets too low. It works from a priority list, and the list is the part you decide.

The logic, step by step

The rule is simple to state. Berkeley Lab’s simulation used it in plain form: when the solar and battery system could not meet all loads in an hour, “individual end-uses are dropped, starting with the lowest priority load, until remaining loads fully served”. Real controllers apply the same idea faster and on more triggers:

  1. A power trigger. When the total draw approaches the battery’s continuous rating, the controller opens the lowest-priority managed circuit first, then the next.
  2. An energy trigger. When the state of charge falls to a set level, it drops discretionary circuits to stretch what is left for essentials.
  3. A lockout. Some setups prevent one large load from starting while another runs, such as the dryer and the water heater.
  4. A restore rule. Circuits come back in priority order when power or charge allows.

What the equipment makers describe

Manufacturers describe the same idea in their own terms. Enphase’s IQ Batteries page describes an integrated load controller that lets owners “turn power-hungry appliances on and off from the Enphase App to save your charge during an outage”, either automatically by preference or manually. SPAN, a maker of smart electrical panels, says its panel lets owners “change room and appliance priorities on the fly” and “automatically avoids unexpected battery drains and overloads before they happen”. Which devices can work together in your home is something only the installer can confirm.

Build your priority list in tiers

Whether a controller or a person does the shedding, the priority list should be written before the outage. Four tiers cover most homes:

Tier Loads Rule in an outage
1. Never shed Medical equipment, sump pump in wet weather, refrigerator and freezer, network and phone charging Always on while the battery has charge
2. Keep if possible Furnace blower in cold weather, a few lighting circuits, a well pump on a schedule Shed only when the battery falls to a set level
3. Comfort Air conditioner or heat pump, electric water heater, microwave Run one at a time, and only with charge to spare or solar coming in
4. Wait for the grid Dryer, range and oven, EV charger, pool pump, spare freezers Off for the whole outage

The tiers also sort what belongs on a critical-loads subpanel: tiers 1 and 2, and a tier 3 load only if the battery’s power and surge allow it.

Manual shedding still counts

Without a controller, you are the load manager. A short, printed list beside the panel (“in an outage, switch off: dryer, range, water heater, EV charger; run the microwave only with the AC off”) does the same job, more slowly and only while someone is home. It is a reasonable start for a partial-backup home that wants to add one larger circuit.

The big loads, one by one

Most homes can back up the small loads with a single battery. The decision is really about six to eight large loads, each limited by a different one of the three constraints. Read each appliance’s nameplate for its running watts or amps and, for motors, its LRA.

Load Which limit bites first Usual options
Central air conditioner or heat pump outdoor unit Surge at start, then energy over hours Check LRA against surge; soft starter; more battery units; run only in daytime with solar; or exclude
Electric heat strips in an air handler Continuous power and energy Usually excluded or locked out; a heat pump without strips is far easier to carry
Electric range and oven Continuous power Shed automatically, or use a single small appliance (microwave, induction plate) on a 120 V outlet instead
Electric clothes dryer Continuous power and energy Excluded or shed; it can wait for the grid
Electric tank water heater Continuous power and energy Heat the tank before a storm and switch it off; or lock it out while other large loads run
Well pump Surge at start Check LRA against surge; a pump that cannot start leaves the house without water
Sump pump Surge at start, critical timing Usually on the critical list; check its start against surge
EV charger Continuous power and energy Exclude or set a low current limit; most residential Level 2 chargers operate at up to 30 A, delivering 7.2 kW

The EV figure comes from the DOE Alternative Fuels Data Center, which states that “most residential Level 2 chargers operate at up to 30 Amps, delivering 7.2 kW”. That alone exceeds a 5 kW battery’s continuous rating. Charging the car from the house battery in an outage only makes sense where the equipment is designed for it and the charging current can be turned down.

Gas appliances change the picture in your favor. A gas furnace needs only its blower and controls on the backup, and a gas water heater or range may need little electricity or none. An all-electric home has more large loads to manage, which is one reason electrification and backup planning belong in the same conversation, along with the panel capacity questions in going all-electric on a 100-amp panel.

Medical equipment comes first

Power-dependent medical equipment belongs on the backed-up circuits before any comfort load, and it needs a plan that does not depend on one battery alone. Ready.gov’s power outage guidance asks households to “talk to your medical provider about a power outage plan for medical devices powered by electricity” and to have alternate plans for refrigerating medicines. Note each device’s watts and hours on your load list, and make sure its outlet is on a circuit the battery actually feeds.

A worked example: partial and whole-home on the same battery

The same battery gives very different results depending on what it is asked to run. This example uses the site’s fictional example battery and the battery sizing worksheet’s default load list.

Example (fictional). The example home’s battery holds 13.5 kWh usable, delivers 5 kW continuously and keeps a 20% reserve (2.7 kWh). Its critical-loads list, the battery sizing worksheet default, has seven loads: a refrigerator averaging 150 W for 10 hours, a gas furnace blower at 500 W for 8 hours, a sump pump at 800 W for 1 hour, a router at 20 W for 24 hours, LED lights at 60 W for 6 hours, phone and laptop charging at 100 W for 3 hours, and a microwave at 1,200 W for 0.3 hours.

Partial backup. Daily energy: 1.5 + 4.0 + 0.8 + 0.48 + 0.36 + 0.3 + 0.36 = 7.8 kWh. If every load ran at once: 150 + 500 + 800 + 20 + 60 + 100 + 1,200 = 2,830 W, well inside 5 kW. The average load is 7.8 ÷ 24 = 0.325 kW, which the calculator rounds to 330 W. Starting at the reserve, the battery has 2.7 × 0.95 = 2.57 kWh for the loads, about 7.8 hours at 0.33 kW. Starting full, it has 13.5 × 0.95 = 12.8 kWh, about 38.9 hours, with no solar recharging.

Whole-home, summer afternoon. Now suppose the same battery is wired to the main panel, and the home’s central air conditioner draws 3.0 kW while running (an invented nameplate figure for the example) and runs half of each hour for 12 hours. Adding it raises daily energy by 3.0 × 12 × 0.5 = 18 kWh, to 25.8 kWh, and the average load to 25.8 ÷ 24 = 1.08 kW. Starting full, the battery lasts 12.8 ÷ 1.08 = 11.9 hours. Starting at the reserve, 2.57 ÷ 1.08 = 2.4 hours.

Power check. With the air conditioner running, the other loads can add at most 2.0 kW before the total reaches 5 kW. The microwave (1.2 kW) and sump pump (0.8 kW) together would take it to exactly 5.0 kW, before the furnace blower, refrigerator and lights. A load controller that blocks the microwave while the compressor runs keeps the total at 3.0 + 1.63 = 4.63 kW with everything else on.

Start check. The 3.0 kW figure is the running draw. Whether the compressor can start depends on its LRA against the battery’s surge capability, which this fictional battery’s sheet would have to state.

The example shows the shape of the trade. Partial backup on this battery lasts more than a day from full. Whole-home backup with air conditioning lasts about half a day from full and under three hours from the everyday reserve, and it needs a load rule to stay inside the power limit. Neither is wrong; they answer different questions. The backup runtime calculator reproduces the hours for your own loads.

Solar, a second battery and the panel itself

Three things change what a battery system can run beyond its own spec sheet: whether solar recharges it during an outage, whether more units are added, and what the home’s electrical service and panel can carry.

Solar during an outage

Whether the panels keep producing and recharging the battery when the grid is down depends on how the system was designed and installed. Where they can, sunny days refill part of the battery and change multi-day arithmetic completely; where they cannot, the battery’s stored kWh are all there is. Why that is, and what makes the difference, is the subject of why solar panels shut off in a power outage. Ask the installer whether your panels recharge the battery when the grid is down, and at what point a nearly empty battery stops supporting them.

Adding battery units

Adding units adds usable kWh, and on most systems it also adds continuous power, because each unit brings its own inverter or power stage. How the ratings combine, including surge, is in the maker’s design documentation and the installer’s system design; do not assume surge figures simply add. FranklinWH’s page, for example, says up to 15 aPower units can connect to one of its gateways, for 204 kWh; few homes need anything like that, but it shows that energy scales more easily than the wiring and controls around it.

The panel, the service and the code

Whole-home backup routes the house’s full load through the backup equipment, so the size of the main panel and service matters. A home with a 100-amp service planning heat pumps and an EV faces load questions before the battery enters the picture; the 100-amp panel article works through them.

Wiring for backup follows the National Electrical Code (NFPA 70) in the edition your state or local jurisdiction has adopted, as applied by your electrician and inspector. In Kentucky, the net metering statute adds that customer generating systems and interconnection equipment “shall meet all applicable safety and power quality standards established by the National Electrical Code (NEC), Institute of Electrical and Electronics Engineers (IEEE), and accredited testing laboratories such as Underwriters Laboratories” (KRS 278.466(7)). Which arrangement is allowed for your home, and how loads must be calculated, is the electrician’s and the inspector’s call, not a homeowner setting.

Questions to settle with your installer

Most backup disappointments trace back to a question nobody asked before installation. Take these to the installer, with your load list and the nameplates of your largest motors.

  1. Is the backup whole-home, a critical-loads subpanel, or none? Ask for the drawing that shows it.
  2. Which circuits are backed up? Get the list in writing and label the panel.
  3. What is the system’s continuous rating, in kW and in amps at 240 V, with the number of units installed?
  4. Can it start my largest motors? Give the LRA of the air conditioner or heat pump, the well pump and the sump pump, and ask for the answer with the other backed-up loads running.
  5. Is there load management? If so, which circuits does it shed, in what order, and can I change the priorities?
  6. What happens if the load exceeds the rating? And how do I restore backup power if it trips?
  7. Does solar recharge the battery during an outage?
  8. What reserve is set, and can a storm mode raise it? The reserve is where backup hours start on an ordinary evening.

How a schedule fits around the wiring

A schedule cannot change what is wired to the battery, and it should not try. What it can do is make sure the battery starts an outage as full as the day allows, and tell you in advance how long the loads you list will last at the reserve you choose.

Culni is home energy software that reads a home’s electricity rate and runs one daily schedule across rooftop solar, a home battery, EV charging and flexible loads, then checks the result against the bill each month. Its backup reserve feature works with the backup your installer set up: it never schedules the battery below the reserve you choose, can raise it before forecast storms, and states the hours of backup for the loads you list. It does not change wiring, backup panels or transfer equipment, and which devices can follow a schedule is confirmed home by home, as the devices page explains. The battery homes page covers how backup and daily savings share one battery.

What to do next

  1. List your critical loads in the battery sizing worksheet, with running watts and hours, and note the LRA of every motor you want backed up.
  2. Read your battery’s spec sheet for continuous output, surge or motor-starting capability, and usable capacity, including the footnotes.
  3. Compare the sum of loads that run together with the continuous rating, and each motor’s LRA with the surge rating.
  4. Run the hours in the backup runtime calculator, once starting from your reserve and once from full.
  5. Decide what to shed, by controller or by a printed list at the panel.
  6. Take the installer questions above to the people who wired the system, before storm season.

To have your load list, battery and rate turned into a reserve setting and stated hours of backup for the loads you list, with every assumption written down, you can send your rate and device list.