Backup runtime calculator

Hours of backup for the loads you list, at the charge the battery holds when the outage starts.

You enter
Usable kWh, starting charge, average load, inverter
You get
kWh available, hours and days of backup
Worst case
The outage starts with the battery at its reserve
Leaves out
Solar recharging and motor start-up surges
A lantern glows on a windowsill during a rainstorm, with rain streaking the glass and a dark house across the street.

Calculator

The values filled in describe the fictional example home and an example rate, not a utility tariff. Replace them with your own; results update as you type. Nothing you enter leaves your browser.

Your reserve setting is the worst case: the outage can start right after a peak.
The battery sizing worksheet adds up your critical loads.

Results

Energy available to your loads
2.6 kWh
Hours of backup
7.8 hours
Days of backup
0.3 days
Average load
0.33 kW

Without any solar recharging. Backup only reaches circuits the installer connected to the battery, and motor loads such as well pumps and central air can need more power at start-up than the battery can supply.

How long a battery lasts in an outage depends less on its size than on three other numbers: how full it is when the power goes out, how much the house draws while it is out, and how much is lost in the inverter. This calculator uses all three and gives hours of backup for the loads you list, at the reserve you choose.

What each input means and where to find it

Input What it means Where to find it
Usable battery capacity kWh the battery can deliver The specification sheet or the app
Charge when the outage starts Percentage of usable capacity in the battery at that moment The worst case is your reserve setting in the app, because an outage can start right after the battery has covered the evening peak
Average load during the outage Average watts of the loads that stay on The battery sizing worksheet: daily kWh ÷ 24 × 1,000. Or the home consumption the battery app shows during a quiet hour
Inverter efficiency Share of stored energy that reaches your circuits The inverter’s specification sheet. The default assumes 95%

The formula in plain words

  1. Energy available = usable capacity × starting charge × inverter efficiency.
  2. Hours of backup = energy available ÷ average load in kW (watts ÷ 1,000).
  3. Days of backup = hours ÷ 24.

Example (fictional). The calculator opens with the fictional example home’s battery: 13.5 kWh usable, with the outage starting at its 20% reserve, an average load of 330 watts and 95% inverter efficiency. The energy available to the loads is 2.6 kWh, which gives 7.8 hours of backup, or 0.3 days, at an average load of 0.33 kW. The 330 watts comes from the battery sizing worksheet’s example list: 7.80 kWh a day is an average of 325 watts, rounded up. Change the starting charge to 100% and the same battery gives 12.8 kWh, 38.9 hours, or 1.6 days.

How to read the result

The gap between 7.8 hours and 38.9 hours is the trade-off behind every reserve setting. Each percent kept for outages is a percent not spent covering the peak, and each percent spent at the peak is gone if the power fails that night. Holding a high reserve every day is expensive on a time-of-use rate; holding a low one is a gamble in storm season. Raising the reserve before forecast storms, and lowering it again afterward, gets much of both.

For context, EIA reports that US electricity customers averaged 11 hours of interruptions in 2024, nearly twice the average of the decade before. Major events caused 80% of those hours, while interruptions outside major events routinely average about two hours a year. The long outages arrive with storms, which is exactly when the starting charge matters most.

Limits

  • No solar recharging. On a sunny day, panels can refill part of the battery during an outage if the system is set up to do so. On a cloudy one they may not.
  • Only backed-up circuits count. Backup reaches the circuits your installer connected to the battery. A partial backup panel may not include the loads you assume.
  • Start-up surges are not modeled. Motors such as well pumps, sump pumps and central air can need more power at start-up than the battery can supply. Check the battery’s power rating with your installer.
  • An average hides peaks. A microwave at 1,200 watts barely moves the daily energy, but it adds to the power the battery must deliver at that moment.
  • The battery and its installation decide what is possible. Culni does not change wiring, transfer switches or protection settings.

What to do next

Build your own load list in the battery sizing worksheet, then work through the outage readiness checklist before storm season. To see what a reserve costs in daily savings, run the battery arbitrage calculator at two reserve levels.

Culni’s backup reserve feature sets the everyday reserve with you, can raise it ahead of forecast storms, and states the hours of backup it gives for the loads you list. The battery homes page explains how it fits with the rest of the schedule. To get those hours for your home, check my home.