Home battery warranties: throughput, cycles and what daily use costs

How a home battery warranty's years, cycle counts and MWh throughput caps add up under daily time-of-use cycling, with real warranty terms turned into years.

Reader question
How much of my battery's warranty does daily time-of-use cycling use up, and what do round-trip efficiency and throughput limits mean in practice?
An old stone staircase whose steps are each worn into a shallow dip at the center, beside a brass handrail polished bright where hands rest.

Daily time-of-use cycling shortens a home battery warranty only if your yearly discharge is larger than the warranty’s throughput budget: its cap divided by its years. For the warranties read here, that budget works out to between 0.72 and 0.79 full cycles a day for the throughput caps, and 1.1 discharges a day for a 6,000-cycle cap. Below that rate the warranty ends on its calendar date (10, 12 or 15 years); above it, every extra kWh you discharge brings the end closer. Round-trip efficiency is a separate, daily cost: at 85%, you buy about 1.18 kWh for every kWh the battery gives back.

This guide reads published warranty documents for batteries from three manufacturers, as of November 2026, and converts their limits into years at the cycling rates a time-of-use schedule produces. It then prices the efficiency loss on a bill, shows what grid charging and grid-program events add, and lists the questions to ask before you buy. Brand names appear only because their published terms are quoted; this is not a ranking or an endorsement.

What a home battery warranty actually promises

A home battery warranty usually makes two promises: that the product is free of defects for a period, and that it will still hold a stated share of its original capacity at the end. Enphase calls these the “Workmanship Warranty” and the “Capacity Retention Warranty.” FranklinWH calls them the warranty period and the performance warranty.

The capacity promise is the one daily cycling affects. It ends at the first of up to three limits: a number of years, a number of cycles, or a total amount of energy passed through the battery. Whichever comes first ends coverage, so a battery that runs hard can lose its warranty years before the date printed on the box.

The remedy is narrower than many owners assume. FranklinWH will “repair or replace” a defective device “with an equivalent product (new or refurbished),” and the replacement inherits the remaining warranty period rather than a fresh one. FranklinWH can also refund the purchase price “less reasonable depreciation” in some cases.

Other parts of the system carry their own terms

The battery modules are not the only parts with a warranty, and the other parts can matter more to daily operation. FranklinWH’s document lists separate terms by product: 15 years for the aPower 2 and aPower S, 12 years for the aPower X and its gateway, 25 years for its rapid shutdown device, and “up to 5 years” for the aGate communications module that supports Ethernet, Wi-Fi, 4G and Bluetooth. It adds that this coverage does not extend to the quality or coverage of 4G service where the system is installed.

That last part connects to a condition covered later: several of these warranties require the battery to stay online. A communications part covered for up to five years, in a system whose battery is covered for 12 or 15, is worth knowing about before year six.

The three limits: years, cycles and throughput

Each limit measures something different, and each needs a plain definition before you can compare products.

  • Years. The calendar term, counted from installation or activation. FranklinWH counts from the earlier of the installation date or 12 months after the manufacture date, so a battery that sat in a warehouse starts with less than its full term.
  • Cycles. A count of discharges. Enphase’s documents speak of “discharged cycles” without defining how a partial discharge is counted.
  • Throughput. The total energy that has passed through the battery, written either as a total (FranklinWH’s 60 MWh) or per kWh of capacity (Enphase’s 2.8 MWh per kWh of rated capacity, SolarEdge’s 2.87 MWh per kWh of usable capacity).

One MWh is 1,000 kWh. A throughput cap of 2.8 MWh per kWh of capacity therefore equals 2,800 full discharges of the battery’s rated capacity, if every discharge went from full to empty. That conversion, “equivalent full cycles,” is how this guide compares cycle caps with throughput caps.

Five sets of terms, read in the documents

Battery (warranty document) Years Cycle or throughput cap Capacity promised at the end Equivalent full cycles
Enphase IQ Battery 3, 3T, 10 and 10T (effective November 19, 2021) 10 4,000 discharged cycles, or 2.8 MWh of AC throughput per kWh of rated capacity At least 70% of nameplate 2,800 (from throughput)
Enphase IQ Battery 5P (effective September 1, 2025) 15 6,000 discharged cycles At least 70% at the end of year 10 and 60% at the end of the term 6,000 (cycle count)
FranklinWH aPower 2 and aPower S (effective October 28, 2026) 15 60 MWh aggregate throughput At least 70% of the rated 15 kWh 4,000
FranklinWH aPower X (same document) 12 43 MWh aggregate throughput At least 70% of the rated 13.6 kWh 3,162
SolarEdge Home Battery 48V (archived March 30, 2024) 10 2.87 MWh per kWh of usable capacity 70% “Energy Retention” 2,870

Sources: Enphase IQ Battery warranty, Enphase storage warranty covering the IQ Battery 5P, FranklinWH warranty and SolarEdge Home Battery 48V warranty, read in November 2026. The SolarEdge document was read in a March 30, 2024 archived copy because the live file refuses automated requests; confirm which version covers the model and region you buy.

Definitions that change the math

Three words in these documents decide how fast you use a warranty, and none of the documents read here defines all three. Get the manufacturer’s answer in writing before you rely on any conversion, including the ones in this guide.

Does throughput count energy in, energy out, or both?

Enphase writes “AC energy throughput,” FranklinWH “aggregate energy throughput” and SolarEdge “energy throughput.” None of the three documents says whether charging energy counts as well as discharging energy.

The difference is large. If throughput counts only energy discharged, a battery that delivers 10 kWh a day adds 10 kWh. If it counts both directions, the same day adds roughly 10 kWh out plus the somewhat larger amount needed to charge it, and the cap arrives in a little under half the time. This guide assumes discharged energy only, the reading most favorable to the owner, and says so wherever it matters.

Rated, usable, AC or DC capacity?

The per-kWh caps are multiplied by different capacities. Enphase multiplies by rated capacity, measured as DC charge capacity: 10.08 kWh for the IQ Battery 10, under set test conditions. SolarEdge multiplies by usable capacity. FranklinWH states a total and measures the rated 15 kWh “on a new system at 77ºF and 3 kW charge and discharge power.”

Enphase also counts throughput on the AC side, while its rated capacity is a DC figure. A full discharge delivers less AC energy than the DC rating, because the inverter loses some in conversion. That works slightly in the owner’s favor: it takes a few more full discharges to reach an AC throughput cap than the simple “2,800 cycles” conversion suggests.

What counts as a cycle?

A cycle cap like Enphase’s 6,000 “discharged cycles” for the IQ Battery 5P reads very differently depending on how partial discharges are counted. If two half-depth discharges add up to one cycle, a time-of-use battery with a shallow evening discharge uses the cap slowly. If every discharge, however shallow, counts as one cycle, a schedule that discharges twice a day on winter weekdays spends two cycles on each of those days, however little energy moves.

The worked example later in this guide shows the gap: the same hypothetical year uses a 6,000-cycle cap in about 12.7 years under one reading and 27 years under the other.

How many years daily cycling takes: caps converted

The conversion is one line of arithmetic. Years until a throughput cap = cap in kWh ÷ (kWh discharged per day × days per year). For a cycle cap, years = cycles ÷ (discharges per day × days per year). The warranty ends at the smaller of that result and the calendar term.

For a 10.08 kWh Enphase IQ Battery 10, the throughput cap is 2.8 × 10.08 = 28.2 MWh, or 28,224 kWh. One full discharge a day is 10.08 × 365 = 3,679 kWh a year, so the cap arrives after 28,224 ÷ 3,679 = 7.7 years, well before the 10-year term. At half a cycle a day it would take 15.3 years, so the 10-year term ends coverage first.

Years until each warranty ends at half, one and two full cycles a dayHorizontal bar chart. At half a full cycle a day every warranty runs its full term: 10 years for Enphase IQ Battery 10 and SolarEdge Home Battery 48V, 12 years for FranklinWH aPower X, 15 years for FranklinWH aPower 2 and aPower S and for Enphase IQ Battery 5P. At one full cycle a day the throughput caps end coverage first at 7.7, 7.9, 8.7 and 11.0 years, while the IQ Battery 5P still reaches 15 years. At two full cycles a day coverage ends at 3.8, 3.9, 4.3, 5.5 and 8.2 years.051015years of coverageHalf a cycle a dayOne cycle a dayTwo cycles a dayEnphase IQ Battery 10: 10 years or 2.8 MWh per kWh10.07.73.8SolarEdge Home Battery 48V: 10 years or 2.87 MWh per kWh10.07.93.9FranklinWH aPower X: 12 years or 43 MWh12.08.74.3FranklinWH aPower 2 and aPower S: 15 years or 60 MWh15.011.05.5Enphase IQ Battery 5P: 15 years or 6,000 cycles15.015.08.2
Years until coverage ends, at the smaller of the calendar term and the cycle or throughput cap. A cycle means one discharge of the full rated or usable capacity; throughput is counted as discharged energy only. Sources: Enphase IQ Battery warranty (November 19, 2021) and storage warranty (September 1, 2025), FranklinWH System Limited Warranty (October 28, 2026), SolarEdge Home Battery 48V warranty (archived March 30, 2024), read November 2026.

How many cycles does a home battery get?

Read literally, the documents here give between 2,800 and 6,000 cycles. The two Enphase documents state cycle counts directly: 4,000 discharged cycles for the IQ Battery 3 and 10 (though their throughput cap arrives first, at 2,800 equivalent full cycles) and 6,000 for the IQ Battery 5P. The throughput caps convert to 2,870 full cycles for the SolarEdge 48V, 3,162 for the aPower X and 4,000 for the aPower 2 and aPower S.

Those are warranty limits, not a prediction of when a battery stops working. A battery can keep running after its warranty ends, at whatever capacity it has left, and none of these documents promises anything about that period. The useful comparison is between the cap and your own cycling: a battery that averages half a full cycle a day uses 183 full cycles a year, so 2,800 equivalent cycles would take more than 15 years.

The throughput budget: one number per warranty

Divide the cap by the term and you get the most a battery can discharge each year without the cap arriving before the calendar date. Call it the throughput budget. Stay under it, and daily use does not shorten your warranty; go over it, and the cap decides when coverage ends.

Warranty Cap ÷ term Budget per year Budget per day Full cycles a day
Enphase IQ Battery 10 28,224 kWh ÷ 10 2,822 kWh 7.7 kWh 0.77
SolarEdge Home Battery 48V 2,870 kWh per kWh ÷ 10 287 kWh per kWh of usable capacity 0.79 kWh per kWh 0.79
FranklinWH aPower X 43,000 kWh ÷ 12 3,583 kWh 9.8 kWh 0.72
FranklinWH aPower 2 or aPower S 60,000 kWh ÷ 15 4,000 kWh 11.0 kWh 0.73
Enphase IQ Battery 5P 6,000 cycles ÷ 15 400 cycles 1.1 cycles 1.10 (if counted as full cycles)

The pattern is consistent: the throughput caps read here allow about three quarters of a full cycle a day, averaged over the whole term. A battery that empties itself fully every single day will outrun all four throughput caps; one that discharges about half its capacity on weekdays will not come close.

What time-of-use cycling really uses

A time-of-use schedule rarely uses a full cycle a day. The battery discharges through the peak window on weekdays, often only part of its capacity, and may sit nearly idle on weekends when every hour is off-peak. The site’s fictional example home shows one clear spring weekday: its 13.5 kWh battery draws 7.8 kWh from storage to cover the house from 5 to 9 p.m., about 0.58 of a full cycle.

Rates with two peaks change that. LG&E and KU’s residential time-of-day rates, for example, have one weekday on-peak window in summer (2 to 6 p.m. Eastern daylight time, April to October) but two in winter (6 to 10 a.m. and 6 to 10 p.m. Eastern standard time), according to the utility’s rate page. A battery that covers both winter peaks discharges twice on those days, recharging in between from solar or off-peak grid energy.

Example (fictional). A hypothetical year for a 13.5 kWh battery on a rate with one summer peak and two winter peaks. The day counts and kWh are invented to show the method; they are not the example home’s results and not a forecast.

Day type Days kWh discharged per day kWh per year
Summer-season weekdays, one evening peak 153 8 153 × 8 = 1,224
Winter weekdays, morning and evening peaks 108 13 (5 + 8) 108 × 13 = 1,404
Weekends and holidays, evening self-use only 104 2 104 × 2 = 208
Grid-program events, beyond the normal discharge 40 3 40 × 3 = 120
Total 365 2,956

That is 2,956 ÷ 13.5 = 219 full cycles a year, or 0.60 a day. Against a cap of 2.8 MWh per kWh, which for 13.5 kWh is 37.8 MWh, the cap would last 37,800 ÷ 2,956 = 12.8 years, so a 10-year term ends first. The budget for that warranty is 37,800 ÷ 10 = 3,780 kWh a year, and this year uses 2,956, leaving 824 kWh of headroom.

Under a cap of 60 MWh for a 15 kWh battery (4,000 equivalent full cycles), the same pattern scaled to 13.5 kWh would last 54,000 ÷ 2,956 = 18.3 years, past a 15-year term.

Under a 6,000-cycle cap, the answer depends on the definition. Counted as full-equivalent cycles, 219 a year would take 27 years. Counted as one cycle per discharge, the year has 153 + 216 + 104 = 473 discharges (the program events fall inside existing discharges), and 6,000 ÷ 473 = 12.7 years, inside a 15-year term.

The lesson from the example is about the shape of your year, not the averages. Two-peak winters, frequent grid charging and program events push a battery toward its budget; weekends and shallow summer discharges pull it back. Add up a year by day type before deciding whether a warranty is tight for you.

Round-trip efficiency: the loss you pay every day

Round-trip efficiency is the share of energy you get back out of a battery compared with what you put in. NREL’s 2024 Annual Technology Baseline for residential batteries defines it as “the ratio of useful energy output to useful energy input” and adopts 85% as a representative value (read in a May 15, 2026 archived copy, because the live site did not respond). At 85%, you buy 1 ÷ 0.85 = 1.18 kWh for every kWh the battery delivers.

AC or DC: which number your bill sees

Spec sheets can list two efficiencies. Enphase’s IQ Battery 5P data sheet gives 90% on the AC side and 96% on the DC side, alongside 5.0 kWh of usable capacity and 3.84 kVA of continuous power. A DC figure leaves out the conversion between the battery’s DC side and your home’s AC wiring.

When a battery charges from and discharges to your home’s AC circuits, the AC figure is the one your meter and your bill see. Compare products on the same basis, and if a sheet gives only one number, ask which side it describes.

The loss in dollars

Take the default example in the site’s battery arbitrage calculator: 10.8 kWh delivered at the peak from a 13.5 kWh battery with a 20% reserve. At 85% efficiency, charging it takes 10.8 ÷ 0.85 = 12.7 kWh, so 1.9 kWh is lost. At 90%, it takes 10.8 ÷ 0.90 = 12.0 kWh, and 1.2 kWh is lost.

Charging source and price Loss at 85% (1.9 kWh) Loss at 90% (1.2 kWh)
Off-peak grid energy at 8 cents per kWh 1.9 × $0.08 = $0.15 1.2 × $0.08 = $0.10
Solar that would earn a 7 cent export credit 1.9 × $0.07 = $0.13 1.2 × $0.07 = $0.08

Prices are the site’s fictional example rate, not a utility tariff. Suppose a battery cycles like this on 250 days a year: the loss is 1.9 × 250 = 475 kWh at 85%, or $38 at 8 cents, against 300 kWh and $24 at 90%. The calculator includes the loss in its daily value: 10.8 × $0.31 − 12.7 × $0.07 = $2.46 for the peak day in its example.

Pricing a cycle: what warranty throughput is worth

When the throughput cap is what ends your warranty, each kWh you discharge uses a slice of the coverage you paid for. The slice is easy to price: the battery’s installed cost divided by the warranted throughput. Suppose a hypothetical 13.5 kWh battery cost $10,000 installed and its warranty covers 37.8 MWh: $10,000 ÷ 37,800 kWh = 26.5 cents per kWh discharged.

That number can be larger than the spread a battery earns. In the calculator’s default example, the battery earns $2.46 for 10.8 kWh, or $2.46 ÷ 10.8 = 22.8 cents per kWh delivered. If you charged the full warranty slice against every kWh, that cycle would look like a loss.

The charge only applies above the budget, though. If your yearly discharge stays below cap ÷ term, the calendar ends your coverage first, and an extra kWh does not shorten it.

Your yearly discharge What ends the warranty Warranty cost of one more kWh
Below the throughput budget The calendar term Nothing in warranty terms
Above the throughput budget The cap Installed cost ÷ warranted throughput, per kWh

This is warranty accounting, not a measure of physical wear. Batteries also age with time and temperature, and NREL’s baseline notes that “degradation is a function of this usage rate” in its cost model, which assumes “approximately one cycle per day.” A battery cycled within its budget still loses some capacity; the warranty only sets the floor the manufacturer will stand behind.

Keeping a schedule inside the budget

If your estimate runs over the budget, you do not have to stop cycling. A few changes trim throughput where it earns the least:

  • Skip low-spread days. When the gap between the charging price and the peak price is small, such as a mild weekday or a rate season without a strong peak, the cycle earns little and uses the same throughput as a valuable one.
  • Cover the most expensive window, not every window. On a two-peak winter rate, compare the value of the morning peak with the evening peak. If one is shorter or cheaper, leaving it uncovered saves a full extra discharge on those days.
  • Avoid grid top-ups that only break even. A second cycle that earns a few cents after losses spends as much throughput as a profitable one.
  • Set a cap on program events. If you join a utility program, some let you opt out of individual events; using that option late in the year can keep the total inside the budget.
  • Recheck every year. Rates change, and so does how much you drive, heat or cool. A budget that fit last year may not fit this one.

Each of these is a trade between bill savings now and warranty headroom later. Write the trade down with numbers before you make it.

How grid charging and program events add up

Two choices add discharge beyond what solar self-consumption and the evening peak need: charging from the grid to cover a second peak, and enrolling in a utility battery program.

Grid charging. On a rate with morning and evening winter peaks, a battery that refills from off-peak grid energy between them discharges twice in a day. That is how the hypothetical year above reaches 13 kWh on winter weekdays. Whether the second cycle pays after losses is covered in when to charge a battery from the grid; this guide adds that it also spends throughput.

Program events. A 13.5 kWh battery with a 20% floor can deliver up to 10.8 kWh in a single event. Forty such events would add 40 × 10.8 = 432 kWh a year, 32 full cycles, if the battery would otherwise have stayed full. On a time-of-use schedule, much of that energy would have been discharged anyway, so the extra is smaller (the hypothetical year above counts 3 kWh per event). The virtual power plant guide compares program terms and event costs.

Before adding either, check your year against the budget:

  1. Estimate kWh discharged per day for each day type, as in the example table.
  2. Multiply by the number of days of each type and add them up.
  3. Divide the warranty’s cap by its term.
  4. If step 2 is below step 3, the extra use fits inside the calendar term. If it is above, price the excess with the formula in the previous section.

What else can shorten or void coverage

Cycling is not the only way to lose warranty coverage. The documents read for this guide list several conditions that matter more to most owners than throughput.

Internet connection and registration

  • FranklinWH: the system “must maintain consistent internet connectivity.” After more than 90 consecutive days offline, FranklinWH asks for reconnection; if it is not restored, the warranty “will automatically be reduced to a four-year limited warranty from the initial installation date.” Systems not registered at installation get the same four-year coverage.
  • Enphase, IQ Battery 3 and 10: the products “must be continuously connected to the internet during the warranty period,” except for interruptions outside the owner’s reasonable control, and owners must register within 45 days unless they live in a state such as California or Connecticut that forbids that condition.
  • Enphase, IQ Battery 5P: the 2025 document says the products “should be continuously connected” and keeps the 45-day registration rule.
  • SolarEdge 48V: coverage applies to a battery connected to an approved SolarEdge inverter and the SolarEdge Monitoring Platform “for the entire duration of the Warranty Period.”

Temperature

Enphase’s 2021 terms condition the capacity promise on an average annual internal cell temperature of no more than 35°C (95°F) and on ambient limits: fewer than 438 hours above 39°C (102.2°F) and fewer than 160 hours above 49°C (120.2°F) in any 12-month period, and never above 54°C (129.2°F). SolarEdge requires an ambient temperature between 0°C and 40°C for no less than 95% of the warranty period. Where the battery is mounted matters as much as how it is cycled.

Operating modes and who controls the battery

SolarEdge’s 48V warranty covers a battery “used solely for standard solar use” in listed modes: self-consumption, time of use, peak shaving, backup, or “SolarEdge-managed Grid Services or approved 3rd party management systems.” If any outside software or program will control your battery, ask the manufacturer in writing whether that control path is covered.

Installation, moving and selling the house

FranklinWH covers products bought from an authorized reseller and installed by a FranklinWH-certified installer, and excludes removal or relocation without written consent. Enphase transfers coverage to a new owner only if the buyer submits a Change of Ownership Form and pays a transfer fee within 30 days. SolarEdge’s 48V warranty may be transferred to a buyer for the remaining period. FranklinWH also states its products are not designed for life-support or medical equipment.

Claims and deadlines

Enphase asks for claims within 90 days of discovering a defect; FranklinWH asks for defects to be reported within two weeks. FranklinWH also says a new version of its warranty applies only to products ordered after it is published, so keep the version that was current on your order date.

What 70% capacity means for your schedule

Most of the warranties above promise 70% of the original capacity at the end of the term; the IQ Battery 5P promises 70% at year 10 and 60% at year 15. On a 13.5 kWh battery, 70% is 13.5 × 0.70 = 9.45 kWh. A warranty claim needs the battery to fall below that floor before the end, measured the way the warranty specifies, so a battery at 75% after ten years is working as promised.

Example (fictional). The site’s example home has a 13.5 kWh battery with a 2.7 kWh reserve and an example rate with a 31 cent peak from 4 to 9 p.m. On its clear April weekday, the schedule draws 7.8 kWh from storage to cover the peak and ends with 5.7 kWh.

Suppose the same battery had faded to 70%, 9.45 kWh, and the owner kept the same 2.7 kWh reserve. Above the reserve it would hold 9.45 − 2.7 = 6.75 kWh, which is 7.8 − 6.75 = 1.05 kWh short of what the peak used. At about 92.2% one-way efficiency, that is 1.05 × 0.922 = 0.97 kWh the house would buy at peak: 0.97 × $0.31 = $0.30 for the day.

One clear spring weekday is not a month or a year; cloudy days, winter, weekends and the real rate all change the result.

The documents also say how capacity is checked, and the method affects any claim. FranklinWH measures rated capacity “on a new system at 77ºF” and at a set charge and discharge power. SolarEdge says that when modules are added later, energy retention is measured on the oldest module still under warranty, and that modules whose warranty has expired should be disconnected during the measurement. A capacity reading from an app on a cold morning is not the test the warranty uses.

The Enphase IQ Battery 5P terms show something else: a two-step promise of 70% at year 10 and 60% at year 15. Read together, they suggest capacity is expected to keep falling through the second half of the term, so a schedule written for year one will need adjusting long before year fifteen.

As capacity fades, the reserve takes a larger share of a smaller battery. A plan that sets the reserve as a fixed kWh figure for the loads you list, rather than a percentage chosen once at installation, keeps your backup honest as the battery ages. The battery scheduling page explains how a daily schedule works around the reserve.

Questions to ask before you buy

How to read the warranty document yourself

A battery warranty runs from a few pages to more than ten, and the parts that matter are in predictable places. Reading them in this order takes about ten minutes.

  1. Find the covered products list. Check that your exact model or SKU is named. Enphase’s 2025 document applies “only for the Covered Product SKUs” in its schedule.
  2. Find when the term starts. It may be activation, installation or a date tied to manufacture or shipment. Write down which.
  3. Find the end conditions. Look for “whichever comes first” or “the earlier of,” and list every limit.
  4. Find the capacity clause. Note the percentage, when it applies, and how capacity is measured.
  5. Find the conditions. Internet connection, registration deadlines, temperature limits, approved installers and approved modes of operation.
  6. Read the exclusions. Moving the battery, unauthorized repairs, power surges and environmental damage are common.
  7. Read the claim procedure. Note deadlines for reporting a defect and who pays for labor.
  8. Read the transfer clause. Note the form and fee needed when you sell the house.

What to ask the installer

Take these to the installer and ask for written answers that point to the warranty document by name and date. The home battery checklist covers the rest of the purchase, and planning a system covers the questions to settle before buying anything.

  1. Which warranty document covers this exact model, and what is its effective date? Ask for a copy of the version current on your order date.
  2. What are the years, the cycle cap and the throughput cap? Write all three.
  3. Is throughput counted as energy discharged, energy charged, or both?
  4. Is the per-kWh cap multiplied by rated, usable, AC or DC capacity?
  5. How is a partial discharge counted against a cycle cap?
  6. What capacity is promised at the end, and how is it measured? FranklinWH, for example, measures rated capacity at 77°F and a set charge and discharge power.
  7. What happens if the battery goes offline? Note any reduction in the term, as in FranklinWH’s four-year fallback.
  8. Are grid-program events and third-party control covered? Ask by program name if you plan to join one.
  9. What temperature limits apply, and does the planned location meet them?
  10. How is the warranty transferred if you sell the house, and what does it cost?
  11. What round-trip efficiency applies on the AC side?
  12. Where can you see lifetime discharged energy? Ask whether the app or the installer can report it, so you can track it against the budget.

What to do next

Work out your own throughput budget before you set a schedule. Divide your warranty’s cap by its term, then estimate your yearly discharge by day type: summer weekdays, winter weekdays, weekends and any program events. If the year comes in under the budget, the warranty is not what limits your schedule; the rate and the reserve are.

Then put the efficiency loss and the peak value side by side in the battery arbitrage calculator using your own rate. If you are weighing a second daily cycle, read when to charge a battery from the grid; if you are weighing a utility program, read the virtual power plant guide.

Culni writes a daily schedule for a home’s battery from its electricity rate, within the manufacturer’s limits and above the reserve you choose. Its home energy plan includes an hour-by-hour schedule for each day type, which shows how much the battery would discharge on each, so you can compare it with your warranty’s budget. To get one for your home, send your rate plan, a recent bill, your battery model and its warranty document through the contact page.