Is a standard 120-volt outlet enough for my driving, or do I need Level 2, given the hours my rate's off-peak window allows?
A narrow garden spade and a wide snow shovel lean against a fence post at first light beside a freshly cleared path through deep snow that ends at a closed shed door.

A standard 120-volt outlet is enough when the kWh your daily miles need fit inside the off-peak hours between plugging in and leaving, with room left for cold weeks; you need Level 2 when they do not. A Level 1 cord adds roughly 1.4 to 1.9 kW, which the Department of Energy puts at about 5 miles of range per hour, so an eight-hour off-peak window gives a car that uses 31 kWh per 100 miles about 37 to 49 miles in mild weather. A Level 2 charger at 7.2 kW fills the same eight hours with about 186 miles, which is why the real question is not “Level 1 or Level 2” but “how many cheap hours do I get, and how many miles must they cover”.

Most comparison pages count the hours you are home overnight. On a time-of-use rate that is the wrong clock: the hours that matter are the ones inside the low-price window, and on several real tariffs that window is seven and a half or eight hours, not thirteen. This article walks through that check, the 120-volt circuit details that decide whether Level 1 is safe to use every night, and the cases where a 240-volt charger pays for itself in convenience. Charger amperage and panel capacity are covered in EV charger amps and your panel; the choice of rate is in the best electricity rate for EV charging.

Level 1 and Level 2 in numbers

Level 1 is AC charging from a 120-volt household outlet through the cord set that comes with most EVs; Level 2 is AC charging from a 240-volt circuit through a wall-mounted or plug-in charger. Both feed the car’s own onboard charger, which converts AC to DC for the battery, so the car sets the upper limit on how fast either one can go.

The Department of Energy’s Alternative Fuels Data Center (AFDC) and the EPA’s home charging guide give the standard figures:

Level 1 Level 2
Supply 120 V AC household outlet 240 V AC at home (208 V is typical in commercial buildings)
Typical current (EPA) 8 to 16 amps 16 to 80 amps; 30 to 40 amps is more common
Power About 1.9 kW in the AFDC’s estimate “Most residential Level 2 chargers operate at up to 30 Amps, delivering 7.2 kW”; units range from 2.9 to 19.2 kW
Range added per hour About 5 miles (AFDC); 3 to 5 miles (EPA) About 25 miles (AFDC); 25 to 40 miles (EPA)
Equipment The portable cord set that comes with most EVs A charger bought and installed, or a higher-power portable unit on a 240 V outlet
Circuit An outlet on a dedicated branch circuit is what the AFDC describes A dedicated 240 V circuit sized for the charger; the AFDC notes a 30-amp unit needs a dedicated 40-amp circuit

The connector is the same for both levels. The AFDC explains that a Level 1 cord set has a household NEMA plug on one end and an SAE J1772 connector on the other, that “Level 2 charging equipment uses the same J1772 connector that Level 1 equipment uses”, and that “All commercially available EVs in the United States have the ability to charge using Level 1 and Level 2 charging equipment.” Vehicles with the J3400 (NACS) port, which began with Tesla, use it for every level and come with a J1772 adapter for other Level 2 equipment.

Power, energy and range: the units that matter

Power is a rate, in kW; energy is an amount, in kWh. Volts times amps gives watts: a cord drawing 12 amps at 120 volts draws 1,440 watts, or 1.44 kW, and one drawing 16 amps draws 1.92 kW, close to the AFDC’s 1.9 kW assumption. A Level 2 charger drawing 30 amps at 240 volts draws 7.2 kW. Multiply kW by hours to get the kWh the car receives from the wall, then divide by the car’s kWh per mile to get miles.

Why the off-peak window, not the night, sets the limit

On a time-of-use rate, the useful charging time is the overlap between the hours the car is parked and the hours the rate is cheap. A car that is home from 6 p.m. to 7:30 a.m. is plugged in for 13.5 hours, but on most of the tariffs below it gets seven and a half to ten cheap hours, and on one it gets all of them.

Here is that overlap for a car that plugs in at 6 p.m. and leaves at 7:30 a.m. on a weekday, using each utility’s published windows as of November 2026:

  • Example rate (fictional): off-peak runs 9 p.m. to 7 a.m., so the car gets 10 hours.
  • LG&E RTOD-Energy, April through October: the tariff’s rating periods put weekday off-peak from 5 p.m. to 1 p.m. Eastern Standard Time, which is 6 p.m. to 2 p.m. on the clock during daylight saving time. Every one of the 13.5 hours is off-peak.
  • LG&E RTOD-Energy, November through March: weekday on-peak runs 6 a.m. to 10 a.m. and 6 p.m. to 10 p.m., so the car gets 10 p.m. to 6 a.m.: 8 hours. In the weeks after daylight saving time begins in March and before it ends in November, LG&E’s time-of-day page shows the same windows an hour later on the clock, 11 p.m. to 7 a.m., still 8 hours.
  • PG&E EV2-A: Schedule EV2 puts peak at 4 p.m. to 9 p.m. and partial-peak at 9 p.m. to midnight, so off-peak starts at midnight. The car gets 7.5 hours before a 7:30 a.m. departure.
  • PG&E EV-B, a separately metered EV rate: Schedule EV puts weekday off-peak from 11 p.m. to 7 a.m., 8 hours.
  • Con Edison residential time-of-use: the utility’s EV rate page shows off-peak from midnight to 8 a.m., so the car gets 7.5 hours.
Off-peak hours between a 6 p.m. plug-in and a 7:30 a.m. departure on six ratesTimelines from 6 p.m. to 7:30 a.m. The fictional example rate gives 10 off-peak hours, LG&E RTOD-Energy gives 13.5 hours on a summer weekday and 8 hours on a winter weekday, PG&E EV2-A gives 7.5 hours, PG&E EV-B gives 8 hours on a weekday, and Con Edison time-of-use gives 7.5 hours. Cheap hours while the car is parked (weekday, clock time) Example rate (fictional) 10 h LG&E RTOD, summer 13.5 h LG&E RTOD, winter 8 h PG&E EV2-A 7.5 h PG&E EV-B 8 h Con Edison TOU 7.5 h 6 p.m. 9 p.m. 12 a.m. 3 a.m. 6 a.m. Off-peak Part-peak or day Peak or on-peak
Weekday windows in clock time for a car parked from 6 p.m. to 7:30 a.m. Sources: LG&E tariff Sheet No. 6.1 (rating periods in EST, shown here in clock time) and the LG&E and KU time-of-day page; PG&E Schedules EV2 and EV; Con Edison EV rate page; the example rate is fictional. Checked November 2026.

Two things follow. First, the same household can need Level 2 in one season and not the other: on LG&E’s rate, a summer weekday gives 13.5 cheap hours and a winter weekday gives 8. Second, an earlier departure or a later off-peak start cuts the window faster than most people expect. Leave at 6:30 a.m. on Con Edison’s rate and the window is six and a half hours.

Weekends change the arithmetic on some rates. LG&E’s RTOD-Energy is off-peak all day on Saturdays and Sundays, which gives a slow charger extra hours to make up a weekday shortfall. PG&E’s EV2-A keeps its 4 p.m. to 9 p.m. peak every day, weekends included, so its overnight window stays the same all week.

How to check whether Level 1 fits your window

The test has four numbers: your daily miles, your car’s kWh per mile, your charger’s kW and the off-peak hours you get. If miles times kWh per mile is less than kW times off-peak hours, with a margin, Level 1 covers you on that day type.

  1. Find your car’s kWh per mile. Use the EPA figure on fueleconomy.gov. The 2026 Chevrolet Equinox EV FWD is rated at 31 kWh per 100 miles, or 0.31 kWh per mile. The EPA says its MPGe values include charging losses and assume Level 2 AC charging, so the figure is already measured from the wall for Level 2.
  2. Work out the daily need. Multiply daily miles by kWh per mile. 35 miles x 0.31 = 10.85 kWh.
  3. Find your charger’s kW. For Level 1, multiply 120 volts by the cord’s amp setting: 12 amps gives 1.44 kW. For Level 2, use the charger’s rating or setting, capped by the car’s onboard charger.
  4. Count your off-peak hours. Count only the overlap between plug-in and departure and the cheap window, for each day type: summer weekday, winter weekday, weekend.
  5. Compare with a margin. Hours needed = kWh needed / kW. 10.85 kWh / 1.44 kW = 7.5 hours, which just fits an 8-hour window and leaves almost nothing for a cold night or an extra errand.

The EV charging time calculator does step 5 for any kWh, charger power and charging loss. With its default inputs of 40 kWh to add, a 7.2 kW charger, a 10% charging loss and 1.9 kW for Level 1, it returns 6.2 hours at 7.2 kW and 23.4 hours on Level 1, with 44.4 kWh drawn from the wall. That 40 kWh is roughly what a long day trip uses, and it is the case where Level 1 takes three nights and Level 2 takes one.

What each charger can add inside common windows

The table below turns charger power and window length into miles of range for a car using 31 kWh per 100 miles in mild weather. It uses kW x hours = kWh, then kWh / 0.31 = miles.

Charger7.5 hours8 hours10 hours13.5 hours8 hours on a 20°F day
Level 1 at 12 A (1.44 kW)35 miles37 miles46 miles63 miles23 miles
Level 1 at 1.9 kW (AFDC estimate)46 miles49 miles61 miles83 miles30 miles
Level 2 at 16 A (3.84 kW)93 miles99 miles124 miles167 miles60 miles
Level 2 at 30 A (7.2 kW)174 miles186 miles232 miles314 miles113 miles
Miles = kW x hours / 0.31 kWh per mile (2026 Chevrolet Equinox EV FWD, 31 kWh per 100 miles, fueleconomy.gov). The 20°F column uses 0.508 kWh per mile, from the roughly 39% drop in EV fuel economy that fueleconomy.gov reports for 20°F with the cabin heater in use. Charger powers from the AFDC and EPA home charging pages. Checked November 2026.

Read the table against your own day. A driver covering 30 miles a day in mild weather is inside every Level 1 cell. A driver covering 45 miles is inside only the longer windows at the higher Level 1 power. Anyone driving 60 miles a day or more, or charging two cars, needs Level 2 on every window shown.

Example (fictional). The example home’s car drives 35 miles a day at 3.5 miles per kWh with a 10% charging loss, so it draws 11.1 kWh from the wall a day. The example rate’s off-peak window runs 9 p.m. to 7 a.m., ten hours. At the AFDC’s 1.9 kW, Level 1 needs 11.1 / 1.9 = 5.8 hours; at 1.44 kW from a 12-amp cord it needs 11.1 / 1.44 = 7.7 hours. Both fit inside ten hours on a normal day, and the home’s 7.2 kW Level 2 charger needs only 11.1 / 7.2 = 1.5 hours, which is why the example home schedules it from 1 to 3 a.m. On this one fictional rate and this one driving pattern, Level 1 would work most days; the 40 kWh day trip in the calculator’s default would not.

What running short costs on a time-of-use rate

When Level 1 cannot finish inside the window, the rest of the charge lands in a more expensive hour, and you can price that shortfall. On PG&E’s EV2-A in summer, each kWh that spills from off-peak into the 9 p.m. to midnight partial-peak costs $0.42760 minus $0.22558, or 20.2 cents more (Schedule EV2, Sheet 2, effective June 1, 2026). On LG&E’s RTOD-Energy, each kWh pushed into on-peak costs $0.19307 minus $0.09312, or about 10.0 cents more (base energy charges before riders and taxes, effective September 1, 2026).

Suppose a car using 0.31 kWh per mile drives 45 miles a day on EV2-A and leaves at 7:30 a.m. It needs 45 x 0.31 = 13.95 kWh. A 12-amp cord adds 1.44 x 7.5 = 10.8 kWh between midnight and departure, so 3.15 kWh has to come from partial-peak. That costs 3.15 x $0.20202 = $0.64 more a day, or about $19.09 over a 30-day summer month. Set that monthly figure against an electrician’s quote for a 240-volt circuit, and you have a payback period in months rather than a rule of thumb.

Cold weather shrinks what Level 1 can cover

Cold weather raises the kWh a car needs per mile, so the same off-peak window covers fewer miles in January than in April. That matters most on rates where the winter window is also the shortest.

fueleconomy.gov reports, from a 2019 AAA study, that EV fuel economy “can drop roughly 39% in mixed city and highway driving” at 20°F compared with about 77°F, and that range can drop by 41%. About two-thirds of the extra energy goes to heating the cabin. With the cabin heater off, the same page puts the drop at 8% for fuel economy and about 12% for range. It also notes that “preheating the cabin while plugged into the charger can extend your vehicle’s range”, which shifts some heating energy into the charging window.

A 39% drop in miles per kWh means each mile needs 1 / 0.61 = 1.64 times the energy. For the 31 kWh per 100 mile car, that is about 0.508 kWh per mile on a 20°F day with the heater on. A 35-mile day then needs 35 x 0.508 = 17.8 kWh instead of 10.85 kWh.

Do the arithmetic by the week, not the night

A slow charger can run short on cold weeknights and still keep up if the weekend gives it long off-peak hours. Checking a week at a time shows whether the deficit is real.

Suppose a household on LG&E’s RTOD-Energy drives 35 miles every day of a cold week at 20°F and charges from a 12-amp Level 1 cord. The car needs 7 x 17.8 = 124.6 kWh for the week. The five weeknight windows of 8 hours give 5 x 8 x 1.44 = 57.6 kWh. If the car is parked and plugged in for 20 hours on each weekend day, when every hour is off-peak, it gets another 40 x 1.44 = 57.6 kWh. The total, 115.2 kWh, is 9.4 kWh short of the week’s need, about 18 miles at the cold-weather rate.

The same week in mild weather needs 7 x 10.85 = 76.0 kWh, which the weeknight windows plus about 13 weekend hours cover. So the hypothetical household above does fine on Level 1 from April to October and runs short only in cold snaps, which it can cover by charging into the peak on a few winter mornings, using a public charger, or raising the cord’s current if the circuit allows it. Whether those workarounds are acceptable is the decision. A Level 2 charger at 16 amps would cover the cold week from the weeknight windows alone: 5 x 8 x 3.84 = 153.6 kWh.

Losses on a 120-volt cord

Charging is never 100% efficient, and the loss is not a fixed number. fueleconomy.gov’s energy-flow page shows charging losses of about 10% in its combined estimate and notes that “Charging losses can vary with the specific vehicle, type of charging system used” and conditions. Because the EPA’s kWh per mile figures assume Level 2 charging, treat them as a floor when you plan for Level 1, and check the result against your meter or your car’s charging history after the first few weeks.

Three households run through the check

The same four numbers give different answers for different households. The three below are hypothetical, built from real EPA ratings and real tariff windows, to show how the check works in practice.

Household A: a short commute on a short window. Suppose a household drives a 2026 Nissan LEAF with the 75 kWh battery, which fueleconomy.gov rates at 30 kWh per 100 miles, for 24 miles a day on PG&E’s EV2-A, leaving at 7:30 a.m. The car needs 24 x 0.30 = 7.2 kWh. The window from midnight to 7:30 a.m. is 7.5 hours, and a 12-amp cord needs 7.2 / 1.44 = 5.0 hours. Level 1 fits with two and a half hours to spare, and the cord can start at midnight and finish by 5 a.m.

Household B: a longer commute on a seasonal window. Suppose a household drives a car rated at 31 kWh per 100 miles for 42 miles a day on LG&E’s RTOD-Energy, plugging in at 6 p.m. and leaving at 7:30 a.m. It needs 42 x 0.31 = 13.0 kWh in mild weather, which a 12-amp cord delivers in 9.0 hours: inside the 13.5-hour summer window, but past the 8-hour winter weekday window, which gives only 11.5 kWh. On a 20°F day the need rises to 42 x 0.508 = 21.3 kWh, leaving the cord 9.8 kWh short each weeknight. Pushing that into on-peak hours would cost about 9.8 x $0.09995 = $0.98 more per night at base charges. A 16-amp Level 2 charger at 3.84 kW needs 21.3 / 3.84 = 5.6 hours, inside the winter window even on that cold day. This household’s answer is a lower-amp Level 2.

Household C: two cars and one short window. Suppose a household on Con Edison’s time-of-use rate runs two cars, each driving 35 miles a day at 0.31 kWh per mile, so each needs 10.85 kWh and both leave at 7:30 a.m. The off-peak window is 7.5 hours. Two 12-amp cords on two separate circuits would each add 10.8 kWh, just short of the 10.85 kWh each car needs. A single 7.2 kW Level 2 charger could give one car 21.7 kWh every other night in about 3.0 hours, if each car can cover two days on a charge, or two chargers could share one circuit under load management. This household needs Level 2; how to wire it is a panel question.

None of these answers came from a mileage cutoff. Each came from the window, the car’s rating and the season, which is why two households with the same commute can reach different decisions.

What a 120-volt outlet must be to charge every night

Level 1 draws a steady current for hours at a time, every night, which is a harder job than most household outlets were installed for. The AFDC describes Level 1 as workable for many drivers “provided that a power outlet on a dedicated branch circuit is available near their parking location”, and that condition deserves a check before you rely on it.

  • A dedicated circuit. If the garage outlet shares a circuit with a freezer, a workshop or the lights, the charger and those loads add up. Hyundai’s owner’s manual for its 120-volt portable charger tells owners to “Select a circuit that is not shared with other devices for the best performance” and to lower the charge current if other devices are on the same circuit.
  • A current setting that matches the circuit. The same manual lets the owner step the cord through 6, 8, 10 and 12 amps and pairs each setting with an outlet rating, for example a 14 to 16 amp outlet for the 12-amp setting. Other cord sets may offer a similar control; check the owner’s manual for yours.
  • Continuous load. The AFDC notes that the National Electrical Code treats EV charging as a continuous load, and the EPA’s guide says the breaker should be sized at “at least 125%” of the charger it supplies, citing NEC 625.41. At 120 volts, a 12-amp draw times 125% is 15 amps and a 16-amp draw is 20 amps; your electrician confirms what your circuit and outlet allow under the code your area has adopted.
  • No light-duty extension cords. Hyundai’s manual asks owners to avoid extension cords and, if one is unavoidable, to use a grounded medium to heavy duty cord rated at 15 amps minimum. It also says to stop charging immediately if you notice abnormal conditions such as an odor or smoke.
  • Grounding and condition. The manual requires a grounded outlet. An old, loose or warm receptacle is a reason to call an electrician before the first night of charging, not after.

The cost of Level 1 is close to nothing if this outlet already exists. If it does not, ask the electrician who quotes a dedicated 120-volt circuit to price a 240-volt circuit on the same visit, so you compare the two jobs with one set of measurements. The EV charger installation checklist lists what to settle on that visit.

When Level 2 is worth installing

Level 2 is worth installing when Level 1 cannot cover your worst regular day inside the off-peak window, or when the margin is so thin that one long day or one cold week pushes charging into the peak. The AFDC puts the cases plainly: Level 2 suits “drivers with less regular schedules, longer commutes, or EVs with large batteries that require more than overnight (or the typical dwell time) to fully charge.”

Turn that into specific triggers:

  • Your daily miles exceed the Level 1 cell for your shortest window. On a 7.5-hour window, that is about 35 miles at 12 amps and about 46 miles at 1.9 kW for a 31 kWh per 100 mile car in mild weather.
  • Your winter window is short and your winters are cold. On LG&E’s RTOD-Energy, the 8-hour winter weekday window at 20°F covers about 23 to 30 miles on Level 1.
  • Two cars share the house. Two cars need two windows’ worth of energy, or two charging points, in the same cheap hours.
  • Your schedule is irregular. Late returns, early departures and long weekend trips all cut the window or raise the need.
  • You join a program that requires it. LG&E and KU’s Optimized EV Charging program enrolls a qualifying Level 2 charger or a qualifying EV; if your car is not on its list, a qualifying charger is the way in.
  • You want the car full after a road trip by the next morning. Adding 40 kWh takes about 6.2 hours on 7.2 kW and about 23.4 hours on Level 1, per the time calculator above.

The middle option: a lower-amp Level 2 charger

Level 2 does not have to mean a large circuit. The EPA notes that “A 16-Amp Level 2 charger might perfectly suit your needs if your electrical panel is tight on capacity.” At 240 volts, 16 amps is 3.84 kW, more than twice the AFDC’s Level 1 estimate, and it covers 93 to 167 miles in the windows shown above. For a single car driving under about 90 miles a day, that is enough for the window to stop being the constraint on every window in the table. The panel and circuit side of that choice is in EV charger amps and your panel.

The car sets the ceiling

A charger cannot push more power than the car’s onboard charger accepts. The AFDC lists “the vehicle’s internal charger capacity” among the factors that set charging time, and fueleconomy.gov lists some 2026 models in versions distinguished by their onboard charger, for example the Chevrolet Equinox EV AWD with an 11 kW charger or a 19 kW charger. Check your car’s maximum AC charging power in the owner’s manual before you pay for a charger rated above it.

What it does not change

Level 2 does not lower the price per kWh; the rate does. A Level 2 charger that starts the moment you plug in at 6 p.m. can put the whole charge into the peak, where a slower Level 1 cord would have spread it into cheaper hours. Whichever level you choose, the schedule decides the cost: the EV time-of-use rates article shows the cost per mile on each window.

The federal credit for home charging equipment has ended: the IRS says the Alternative Fuel Vehicle Refueling Property Credit applied to property placed in service at a main home from January 1, 2023, to June 30, 2026. Check state and utility programs separately, and ask a tax professional about anything tax-related.

Level 2 features that matter for off-peak charging

If you install Level 2, a few features decide whether it charges in the cheap hours without daily attention. Most of them are about scheduling and installation rather than speed.

Feature What to look for Why it matters on a time-of-use rate
Scheduling A start time or departure time in the charger’s app, or in the car Without a schedule, charging starts at plug-in, often in the peak
One timer, not two Use either the car’s schedule or the charger’s Two timers set to different hours can leave the car uncharged
Adjustable current A current setting the installer can fix to match the circuit Lets a charger run on a smaller circuit, at a lower kW
Plug-in or hardwired The EPA notes chargers rated at 48 amps or higher are usually required to be hardwired; NEMA 14-50 outlets are a common plug-in choice Plug-in units are easier to swap; hardwired units are needed at higher currents
Safety certification The AFDC and EPA both recommend safety-certified equipment, such as ENERGY STAR certified chargers tested by a nationally recognized testing laboratory Not all chargers sold online are safety certified
Cable length and location A cable that reaches the charge port where you actually park A stretched cable is a hazard and a reason to move the unit
Connectivity Wi-Fi or cellular signal at the mounting spot, if you want app scheduling or a utility program A charger that cannot connect can only run its own timer

The EPA’s guide also lists “Scheduling charging to take advantage of lower off-peak electricity rates, where available” and “Sharing power intelligently with other chargers or household appliances” among the optional features of more advanced units. If your Level 1 cord set has current settings but no timer, like the one in the Hyundai manual described above, the schedule has to live in the car’s charging settings.

A decision table: Level 1, a lower-amp Level 2 or full Level 2

Use this table after you have counted your off-peak hours for each day type and worked out your daily kWh need, including a cold-weather allowance if your winters are cold.

Your numbersEquipment to price firstWhyCheck before deciding
Daily need is under about two-thirds of what Level 1 adds in your shortest off-peak windowLevel 1 on a dedicated outletThe margin covers a cold night or an extra errandThe outlet's circuit, grounding and condition; the cord's amp setting
Daily need fits Level 1 in summer but not on cold winter weeknightsLevel 1 with a weekly check, or a 16-amp Level 2Weekend off-peak hours may cover the gap; a lower-amp Level 2 removes itYour rate's weekend hours; how often cold snaps happen where you live
Daily need is above what Level 1 adds in the shortest windowLevel 2 at 16 to 32 ampsFits the need inside the window with room to sparePanel capacity and circuit size with an electrician
Two EVs, long commutes or frequent road tripsLevel 2, possibly with power sharing between chargersTwo cars or large daily needs share the same cheap hoursLoad calculation; whether one circuit can serve two chargers under load management
Your car's onboard charger is smallThe Level 2 current that matches itA charger rated above the car's limit charges no fasterThe car's maximum AC charging power in the owner's manual
You want a utility managed-charging programWhatever the program qualifies: a listed EV or a listed chargerSome programs enroll either the car or the chargerThe program's device list and event rules
Decision rules built from the window arithmetic in this article; charger figures from the AFDC and EPA home charging pages; program eligibility from the LG&E and KU Optimized EV Charging page. Checked November 2026.

The two-thirds threshold in the first row is a planning margin, not a standard: it leaves room for a cold night, a late arrival or a longer day without pushing charging into the peak. Pick a tighter or looser margin depending on how much your days vary.

Common mistakes in the Level 1 vs Level 2 decision

A few errors show up again and again when households size their charging. Each one makes Level 1 look better or worse than it is.

  • Counting the hours at home instead of the cheap hours. Thirteen hours parked becomes seven and a half on PG&E’s EV2-A or Con Edison’s time-of-use rate.
  • Using the summer window all year. LG&E’s RTOD-Energy gives 13.5 cheap hours on a summer weekday evening and 8 in winter.
  • Ignoring cold weather. On a 20°F day with the heater on, the same miles can need about 1.64 times the energy.
  • Assuming the AFDC’s 1.9 kW. The EPA puts Level 1 cords at 8 to 16 amps; at 12 amps a cord draws 1.44 kW at 120 volts.
  • Buying a charger the car cannot use. The onboard charger sets the ceiling.
  • Forgetting the schedule. A Level 2 charger that starts at plug-in can cost more per mile than a Level 1 cord that charges overnight.
  • Plugging into a shared or worn outlet. Nightly continuous current is the job; the outlet and circuit have to be fit for it.

What to do next

Run the check once for each day type, then decide. A short list keeps it concrete:

  1. Write down your daily miles for a normal weekday, your longest regular day and a typical weekend day.
  2. Look up your car’s kWh per 100 miles on fueleconomy.gov, and its maximum AC charging power in the owner’s manual.
  3. List your rate’s off-peak hours between plug-in and departure for a summer weekday, a winter weekday and a weekend day. The LG&E and KU time-of-day article shows those windows for Kentucky customers.
  4. Put the numbers through the EV charging time calculator, once at mild-weather efficiency and once with the cold-weather allowance.
  5. If Level 1 fits, have the outlet and circuit checked. If it does not, take the EV charger installation checklist to an electrician and ask about a 16 to 32 amp Level 2 circuit.
  6. Set one charging schedule, in the car or the charger, to start inside the off-peak window.

Culni is software that reads a home’s electricity rate and runs one daily schedule across solar, a home battery, EV charging and flexible loads. Its EV charging schedule fits the charge into the cheapest hours that still have the car ready by departure, on Level 1 or Level 2, through the car or the charger where a control path is confirmed for your home. The EV homes page covers households with one or two cars, and if you want the window arithmetic done for your own rate and car, you can send your rate plan, a recent bill and your device list.